11. Output Voltage and Delay Adjustment

1. Adjusting output voltage, counterclockwise direction for rising voltage and clockwise direction for lowering
voltage.
2. Adjusting output voltage sensitivity, counterclockwise direction for decreasing sensitivity and clockwise
direction for direction for increasing sensitivity.
3. Adjusting over-high voltage protection, clockwise direction for rising protection voltage and
counterclockwise direction for lowering protection voltage.
4. Adjusting over-low voltage protection, clockwise direction for rising protection voltage and
counterclockwise direction for lowering protection voltage.
5. and 6. Voltage regulation adjustment delay, to insert into a jump line plug for delaying 3~4 sec to start
adjustment. This may extend the use life of A.V.R. in which environment usually has a –high-low voltage
rapid alteration.
7. Over-high or over-low voltage protection delay, to insert a jump line plug for delaying 0.5~1 sec to start
adjustment. This may avoid A.V.R. from error action then the working environment usually has a suddenly high
voltage happened.