Checking Cooling And Heating Control Operation; Refrigerant Charge; No Charge; Low Charge Cooling - Carrier 48DU Installation Instructions Manual

Infinity 14 single-packaged air conditioner and gas furnace system with puron (r-410a) refrigerant 2 to 5 nominal tons (sizes 024-060)
Hide thumbs Also See for 48DU:
Table of Contents

Advertisement

HEATING INPUT (BTU/HR)*
High Stage
Low Stage
40,000
26,000
60,000
39,000
90,000
58,500
115,000
75,000
130,000
84,500
*Cubit ft of natural gas per hour for gas pressures of .5 psig (14 in. wc) or less and a pressure drop of .5 in. wc (based on a .60 specific gravity gas). Ref: Table 12.2 ANSI
Z223- -2002/NFPA 54- -2002.
IMPORTANT: When evaluating the refrigerant charge, an
indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.

REFRIGERANT CHARGE

The amount of refrigerant charge is listed on the unit rating plate
and/or the physical data table. Refer to the Refrigeration Service
Techniques Manual, Refrigerants Section.

NO CHARGE

Check for leak. Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refrigerant
(refer to system rating plate).

LOW CHARGE COOLING

Use Cooling Charging Chart (Fig. 22). Vary refrigerant until the
conditions of the chart are met. Note that charging charts are
different from type normally used. Charts are based on charging the
units to correct subcooling for the various operating conditions.
Accurate pressure gauge and temperature sensing devices are
required. Connect the pressure gauge to the service port on the
suction line. Mount the temperature sensing device on the suction
line and insulate it so that the outdoor ambient does not affect the
reading. Indoor air CFM must be within the normal operating range
of the unit.
UNIT
SIZE
600
700
800
024
0.005
0.007
0.010
030
0.007
0.010
036
042
048
060
FILTER SIZE
500
600
700
20X20X1
0.05
0.07
0.08
24X30X1
24X36X1
Table
7—Heating Inputs
GAS SUPPLY PRESSURE (IN. WG)
NUMBER OF
ORIFICES
2
3
3
3
3
Table
8—ECM Wet Coil Pressure Drop (in. wg)
STANDARD CFM (SCFM)
900
1000
1100
1200
0.012
0.015
0.012
0.015
0.018
0.021
0.019
0.023
0.027
0.032
0.014
0.017
0.020
0.027
Table
9—Filter Pressure Drop Table (in. wg)
800
900
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
0.1
0.12
0.13
0.14
0.15
0.05
0.6
0.07
0.07
0.06
Natural
Min
Max
4.0
13.0
4.0
13.0
4.0
13.0
4.0
13.0
4.0
13.0

TO USE COOLING CHARGING CHARTS

Take the liquid line temperature and read the manifold pressure
gauges.
Refer to the chart to determine what the liquid line temperature
should be.
NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to Check for Refrigerant Leaks section.
NON- -COMMUNICATING
HEATING MODE: 4- -WIRE THERMOSTAT
This mode of operation is provided only in the case where the UI has
failed or is otherwise unavailable. If communications cannot be
established with the UI, the Infinity furnace board will enable the
standard thermostat input terminals to allow simple thermostatic
control of the 48DU unit.
For control with a standard thermostat, disconnect the ABCD
connectors from both control boards and using No. 18 AWG
color- -coded, insulated type 90°C minimum or equivalent wire,
make the connections between the standard thermostat, the furnace
board, and the HP/AC board per Fig. 21. Recommend the use of
interconnecting wire with 105C, 600V, 2/64" insulation.
The Infinity control will respond to cooling and heating demands
with the maximum safe airflow based on gas furnace output and unit
cooling capacity.
1300
1400
1500
1600
0.024
0.037
0.042
0.047
0.024
0.027
0.031
0.035
0.032
0.036
0.041
0.046
0.029
0.032
CFM
0.08
0.09
0.1
0.07
0.07
0.08
0.09
0.09
25
MANIFOLD PRESSURE (IN. WG)
Natural
High Stage
Low Stage
3.2∼ 3.8
1.4 ∼ 2.0
3.2∼ 3.8
1.4 ∼ 2.0
3.2∼ 3.8
1.4 ∼ 2.0
3.2∼ 3.8
1.4 ∼ 2.0
3.2∼ 3.8
1.4 ∼ 2.0
EMERGENCY
COOLING
1700
1800
1900
2000
0.039
0.043
0.052
0.057
0.063
0.068
0.036
0.040
0.045
0.049
0.10
0.11
0.12
0.13
0.14
/
2100
0.053
0.14

Hide quick links: