Heat resistant material (minimum requirements) with wooden mantel or other combustible projection:
To install the heater with a wooden mantel, shelf or other combustible projection above, first measure the heat resistant mate-
rial shown in Figure 6 then see Table B.
HEAT RESISTANT
MATERIAL
MEASUREMENT
12" or more
8" to less than 12"
Less than 8"
14D9999
Figure 6 - Measuring Heat Resistant Material for Mantel
REQUIREMENTS FOR SAFE INSTALLATION WITH WOODEN MANTEL,
SHELF OR OTHER COMBUSTIBLE PROJECTION
DLX18
Hood not required. Observe profiles (side
elevations) shown in Figure 7, page14.
Install hood and observe profiles shown
in Figure 8, page 14; OR extend heat
resistant material to at least 12" and observe resistant material to at least 12" and observe
profiles shown in Figure 7, page 14.
Extend heat resistant material to at least
8", install hood and observe profiles shown
in Figure 8, page 14; OR extend heat
resistant material to at least 12" and observe resistant material to at least 12" and observe
profiles shown in Figure 7, page 14.
TABLE B - Heat Resistant Material Heights and Mantel Location
CLEARANCES
AND
Hood not required. Observe profile (side
elevations) shown in Figure 9, page 15.
Install hood and observe profiles shown
in Figure 8, page 14; OR extend heat
profiles shown in Figure 9, page 15.
Extend heat resistant material to at least
8", install hood and observe profiles shown
in Figure 8, page 14; OR extend heat
profiles shown in Figure 9, page 15.
HEIGHT REQUIRMENTS
DLX24 AND DLX28