Field Of View; Installation Considerations - Net Safety UV/IRS-H2-A User Manual

Ultraviolet / infrared hydrogen flame detector
Table of Contents

Advertisement

Net Safety Monitoring

Field of View

The area in front of a flame detector, where a standardized flame can be
detected and which is specified by distance and angle off the central axis, is
the Field of View. The referenced flame is moved to 50% of the maximum
on-axis detection distance and then moved off-axis horizontally and
vertically to the limit of detection. These off-axis angle limits specify Field
of View.
Table 2: Field of View Testing
Field of View Testing
Fuel
Size
Hydrogen(H2)
24" Plume
NOTE: Data based on Maximum Sensitivity
Setting.

Installation Considerations

The following should be considered when mounting flame detectors.
 Point detector toward where the flame is expected.
 Ensure an unobstructed view of the area to be monitored.
 Employ more than one detector to ensure the hazard is fully covered.
 The detector should be accessible for cleaning the window/lens and
reflector surfaces.
 Tilt detector downward a minimum of 10 to 20
accumulation which could obscure the detector's viewing window.
 Securely mount detector so as to reduce vibration as much as possible.
MAN-0101 Rev 01 UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X
November 23, 2012
Horizontal
Degrees
128(+65, -63)
°
to reduce dirt and dust
 When located outside, detector sensitivity can be reduced by heavy fog,
rain and/or ice.
 Reduce sensitivity setting if false alarms, related to surrounding activities,
occur (refer to "System Sensitivity" )
 When installed near or on water (such as an off shore platform), be sure to
take into account the low horizon level when tilting detector downward.
 UV radiation, other than that produced by an actual fire, is referred to as
"background UV". An example of a high level of background UV could
be a flare stack situated outside of a building. The UV radiation produced
by this flare, in conjunction with a false alarm IR source, may be
detected as fire when a door to the building is opened. Windows or other
reflective surfaces may also cause unusually high levels of UV radiation
to enter the building from the flare. In a situation like this, the fire
detection system response must be carefully checked and the sensitivity
level adjusted high enough so that this "background UV" will not cause
false alarms.
 UV fire detectors respond to radiation other than ultraviolet. X-rays in
conjunction with a false alarm IR source can activate the detector. Since
X- rays are often used in industrial inspection it may be necessary to
disable the system when inspections are conducted nearby.
 For protection against line surge and extraneous transients, it is required to
install detector wires in a braided flexible conduit less than 5 feet.
Note: CSA approved models (UVIRS-H2-A/AR) are not supplied with a
locking collar. ATEX approved models (UVIRS-H2-A-X/H2-AR-X) are
supplied with locking collar.
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uv/irs-h2-a-xUv/irs-h2-arUv/irs-h2-ar-x

Table of Contents