Appendix E: Uvirs-H2 Data - Net Safety UV/IRS-H2-A User Manual

Ultraviolet / infrared hydrogen flame detector
Table of Contents

Advertisement

Net Safety Monitoring
A
E: UVIRS-H2 DATA
PPENDIX
In Door Interference and false alarm Test
Un-Modulated
without fire
Electrical
No Effect at 5 Ft
Heater(1000W)
300W Halogen
No Effect at 5 Ft
Lamp
40W
No Effect at 5 Ft
Fluorescent
Lamp
70W
Hi
No Effect at 5 Ft
Pressure
Sodium Lamp
250W
Metal
No Effect at 5 Ft
Halide
Out Door Interference and false alarm Test
Un-Modulated
without fire
Direct Sunlight
No Effect
Indirect
No Effect
Sunlight
Arc Welding
No Effect further than
20 Ft. False alarm at
15Ft
MAN-0101 Rev 01 UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X
November 23, 2012
Modulated with out
Un-Modulated with
fire
fire
8mA output at 3Hz, 5
No Effect at 5 Ft
Ft, no effect other
frequency or at 15 Ft
8mA output at 3Hz, 5
No Effect at 5 Ft
Ft, no effect other
frequency or at 15 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
Modulated with out
Un-Modulated with
fire
fire
8mA output at 3Hz,
No Effect
no effect at other
frequency
8mA output at 3Hz,
No Effect
no effect at other
frequency
6mA output at 20 Ft
No Effect farther than
False alarm at 15Ft
20 Ft
Modulated with fire
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
Modulated with fire
No Effect
No Effect
No Effect farther than
20 Ft
26