Condition Status-Current Output - Net Safety UV/IRS-H2-A User Manual

Ultraviolet / infrared hydrogen flame detector
Table of Contents

Advertisement

Net Safety Monitoring
Condition Status—
Current Output
The Current Loop status can also be measured to determine detector
condition.
Test Jacks are available on the Analog board in the Net Safety Multi-Purpose
Junction Box. Refer to MAN-0081 for details. The area must be de-classified
prior to opening the Junction Box. The detector can also be monitored using
the 4-20 mA Signal Output.
MAN-0101 Rev 01 UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X
November 23, 2012
Table 5: Status LEDs and Current Output
LED Status
Current
Green LED
O/P
Internal power
1mA
Fault or
system power
out of range
Automatic or
2mA
manual VI
Test Failure
Power up – 90
3mA
secs start delay
Normal
4mA
Operation
Background
6mA
UV Source
Background
8mA
IR Source
Manual VI
10mA
Testing
Adequate
Manual VI
11mA
Testing Good
Manual VI
12mA
Testing
Excellent
Early Warning
16mA
– Intermittent
UV/IR
detected
Fire
20mA
Confirmed
Red LED
Yellow LED
(PWR)
(Alarm)
(Fault)
OFF
OFF
OFF
Flashing
Solid
OFF
Solid
OFF
Solid
OFF
Solid
OFF
Solid
Solid
Solid
Solid
Solid
Solid
Solid
OFF
OFF
Flashing
Solid
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
16