Linear expansion valve

(1) Operation summary of the linear expansion valve
• Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
LEV
3
2
M
5
1
6
4
<Output pulse signal and the valve operation>
Output
(Phase)
1
2
3
[1
ON
ON
OFF
[2
OFF
ON
ON
[3
OFF
OFF
OFF
[4
OFF
OFF
OFF
(2) Linear expansion valve operation
Close
A
B
Extra tightning (about 32 pulse)
Output
4
5
6
7
8
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
C
Open
500 pulse
Opening a valve
all the way
Pulse number
Gray
[4
Orange
[3
Yellow
[2
Black
[1
Connector LEV-A
Opening a valve : 8
7
Closing a valve : 1
2
The output pulse shifts in above order.
• When linear expansion valve operation stops, all output phase
become OFF.
• When the switch is turned on, 700 pulse closing valve signal will be
sent till it goes to
point in order to define the valve position. (The
A
pulse signal is being sent for about 20 seconds.)
• When the valve moves smoothly, there is no sound or vibration
occurring from the linear expansion valve : however, when the pulse
number moves from
to
B
be heard.
No sound is heard when the pulse number moves from
case coil is burnt out or motor is locked by open-phase.
• Sound can be detected by placing the ear against the screw driver
handle while putting the screw driver to the linear expansion valve.
49
Outdoor controller board
DC12V
1
Drive circuit
[4
3
[3
Red
4
[2
5
[1
6
6
5
4
3
2
1
3
4
5
6
7
8
or when the valve is locked, sound can
A
8
1
to
in
B
A