Mitsubishi Electric MSC-GE20VB Service Manual page 23

Split-type air conditioners
Hide thumbs Also See for MSC-GE20VB:
Table of Contents

Advertisement

10-2. INSTRUCTION OF TROUBLESHOOTING
Start
Indoor unit
operates.
Outdoor unit
does not
operate.
Outdoor unit
MUH/MUX
operates only
Outdoor unit
in "Test run
does not
operation".
operate
even in
"Test run
operation".
Check room
Refer to
temperature
"Check of
thermistor.
outdoor unit".
Refer to 10-6.
"Test point
diagram and
voltage".
MUH/MXZ
2-time flash
Flash ON and
Cause:
OFF at 0.5-
Indoor unit
second intervals
• Trouble of
Cause: Indoor/
room temp-
outdoor unit
erature/
• Mis-wiring/or
indoor coil
trouble of
thermistor
serial signal
Refer to
Check room
10-5.
or
temperature
"How to
thermistor
check
and indoor
mis-wiring/
coil thermis-
and serial
tor.
signal error
Refer to 10-6.
(When
"Test point
outdoor unit
diagram and
does not
voltage".
work)".
1.<The case of the trouble of the serial signal>
When the power is turned off and turned on again, the indication shows "the trouble of mis-wiring".
2."Test run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.
Refer to outdoor unit service manual.
OBH529A
Indoor unit
operates.
Outdoor unit
does not operate
normally.
Outdoor unit
MUH/MXZ
does not
Unit does not
stop even
operate
if indoor unit
normal
stops.
operation in
COOL or
HEAT mode.
MU
Refer to
Check of wiring
"Check of
R.V. coil".
diagram of
outdoor unit
MUH
Refer to
"Check of
outdoor unit".
3-time flash
4-time flash
Cause:
Cause:
Indoor unit
Indoor unit
• Trouble of
• Trouble of
indoor unit
indoor fan
control
motor
system
Replace the
Refer to
indoor
10-5.
electronic
"Check of
control
indoor fan
P.C. board.
motor".
Indoor unit
does not receive
the signal from
remote controller.
Indoor unit
Indoor unit
operates, when
does not operate,
the EMERGENCY
when the
OPERATION
EMERGENCY
switch is pressed.
OPERATION
switch is pressed.
1. Check indoor/
Refer to 10-5.
"Check of
outdoor
remote controller
connecting wire.
and receiver
2. Refer to 10-5.
P.C. board".
"Check of indoor
electronic control
P.C. board".
MUH/MXZ
MXZ
MUH/MXZ
7-time flash
5-time flash
6-time flash
Cause:
Cause:
Cause:
Outdoor unit
Outdoor unit
• Trouble of
• Outdoor
• Trouble of
thermistor
power
in outdoor
system
unit
abnormality
Refer to
Replace the
Refer to
"Check of
"Check of
deicer
inverter/
outdoor
P.C. board
compressor"
thermistor"
and others.
and "Check
and others.
of power
supply".
23
OPERATION INDICATOR
lamp on the indoor unit is
flashing ON and OFF.
10-time flash
Cause:
Outdoor unit
Outdoor unit
MXZ
• Outdoor
outdoor
refrigerant
system
control
abnormality
system
Refer to
outdoor
refrigerant
system
related items.
Indoor unit
operates.
But indoor
unit does not
blow out
cool air.
MUX-2A28/2A59/3A60/
3A63/2A70/4A73VB
Refer to
"Check of
indoor/outdoor
units' connection
and outdoor
unit".