Installation Of Fireplace Insert And Connection To The Chimney; Connecting Piece (Flue Gas Pipe); Protection Of Installation Ceiling (Floor); Floor In Front Of The Fireplace Insert - Haas+Sohn EN13229-W Installation And Operating Manual

Table of Contents

Advertisement

6. Room heating capacity according to DIN 18893:
In this regard, please note the details on the Equipment sheet.
The values relate to rooms which do not correspond to the heat protection regulations. For rooms with a room
volume in excess of 200m
The rated heat output stated
on the equipment
plate with
- favourable
- less favourable
- unfavourable

7. Installation of fireplace insert and connection to the chimney

7.1 Connecting piece (flue gas pipe):

The connecting piece has to be technically
matched to chimney and fireplace insert and be
designed to suit the requirements of DIN 18160
Part 2.
In the case of metal connecting pieces the wall
thickness must be at least 2 mm.
If the connecting piece penetrates components
with combustible building materials (e.g. walls to
be protected), protective measures according to
DIN 18160 Part 1 and Part 2 have to be taken.

7.3 Floor in front of the fireplace insert:

In front of the heating insert the floor of
combustible materials has to be protected through
a sufficiently thick covering of non-combustible
materials or replaced. The minimum dimensions of
3
a heat requirement calculation according to DIN 4701 has to be carried out.
Heating conditions are
adequate for:
Insert
Esprit 185.16
7 kW
144
84
56

7.2 Protection of installation ceiling (floor):

Installation ceilings without adequate transverse
distribution
(e.g.
wooden
protected through an additional 6 cm thick proven
concrete slab and a 6 cm thick heat insulation
layer according to AGI Working Sheet Q 132 in the
area of the heating insert. We recommend you
seek advice from a structural engineer.
If the installation floor has adequate transverse
distribution a 6 cm thick heat insulation layer is
sufficient.
this non-combustible area in front of the firebox
opening are:
To the front in accordance with the height (H) of
the firebox floor above the floor plus 300 mm.,
however at least 500 mm.
To the sides, in accordance with the height (H) of
the firebox floor above the floor plus 200 mm,
however at least 300 mm.
Inserts
Komfort 180.18,
Prestige 181.18,
Exquisit 182.18
Trend 184.18
Opus 186.18
8 kW
186
m
107
m
73
m
ceilings)
must
3
3
3
be
5