(Remote Controller address setting)
(Refer to the Installation Manual which is provided with the remote controller for details.)
• Two remote controllers (including the wireless remote controller) can be connected. However, remote control thermistor setting is not
possible.
• As for [master/slave] setting of remote controller, the automatic setting and manual setting are possible. Since manual setting is priority.
• Two remote controllers, which both are wireless, cannot be connected.
10.3.9. As for timer output
• Connect the timer cord to connector (CN-TIMER) on print circuit board.
10.3.10. Precautions in test run
• The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner may not operate.
• Test operation can be carried out using the remote control unit or at the outdoor unit. (If carrying out test operation at the
outdoor unit, refer to "TEST OPERATION" in the outdoor unit installation manual.)
• If using the remote control unit to carry out test operation, follow the procedure given below.
• First, press the OFF/ON (
• Then press the TEST RUN button within 1 minute of pressing the OFF/ON (
• Next, select the operation modes.
• The temperature of the indoor unit pipes will be shown on the temperature setting display. (At the start of the test
operation, it may take up to 1 minute for air conditioner number, switching time and other displays to appear.)
• After operation modes have been selected, stop the compressor for a moment.
• Press the OFF/ON (
NOTE 1
These units are equipped with connection error prevention circuits. If the units do not operate, it is possible that the connection
error prevention circuits have been operated. In such cases, check that the Indoor/outdoor unit connection wire (connected to
terminals
should then commence.
NOTE 2
Do not short the remote control unit wires to each other. (The protection circuit will be activated and the units will not operate.)
Once the cause of the short is eliminated, normal operation will then be possible.
NOTE 3
When running the units in heating mode during test operation, be sure to run the units in cooling mode first before selecting
this mode. If heating mode is selected first, it may cause problems with operation of the compressor. (Heat pump model only.)
NOTE 4
Test operation should be carried out for a minimum of 5 minutes. (Test operation will be cancelled automatically after 30
minutes.)
NOTE 5
Test operation mode should always be cancelled once test operation itself has been completed.
) button.
) button of the TEST RUN button once more to cancel test operation mode.
,
and
) is connected correctly. If they are connected incorrectly, connect them correctly. Normal operation
43
) button.