HEATING MODE OPERATION

• When room temperature is raised to +6°C higher than the designated temperature, compressor stops.
• When room temperature gets less than +5.3°C higher than the designated temperature, compressor turns on.
• At the start of heating operation, if the room temperature is less than +18°C, additional +1°C is set to the
temperature designated by the remote controller. (Canceled when the compressor first stops.)
• Hot Start Function
To prevent the unpleasant cold air to flow, the air flow speed is determined as shown below according to the
temperature of the indoor heat exchanger.
Temperature,
44
indoor heat
exchanger
38
23
INDOOR FAN
Room
Temperature
Designated
Temperature
Indoor fan
Compressor
: In maximum 4 minutes,the operation proceed to the next steps when the heat
exchanger is not warmed up to the reference temperature shown above.
Super
Stop
Low
low
0.7
6
Max.
Max.
4 min.
4 min.
Super
Stop
Low
low
ON
OPERATION DETAILS
Designated by remote controller
Designated by remote controller
OFF
ON
OFF
– 10 –
ON
OFF
ON
OFF