DRY MODE OPERATION

The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for 360 seconds and the room temperature becomes 1.3°C lower than it was set.
The compressor will re-start when room temperature becomes 0.7°C higher than it was set.
The operational frequency will be set every 120 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.
Designated
temperature
0.7˚C
-1.3˚C
MAX
92Hz
Frequency of
compressor
0
Hz
Indoor fan
MIN 20Hz
Super
Selected speed
low
OPERATION DETAILS
Room temperature
3min.
Stop
Super low
– 8 –
MAX
92Hz
MIN 20Hz
Selected speed