CSDV Series Direct Vent Gas Stove
ADjUSTING THE AIR SHUTTER
The venturi of the burner is equipped with an air shutter. The opening of the venturi has been set
at 1/4" for Natural Gas and fully open for Propane installation at sea level. Natural Gas Models
may be adjusted for high altitude as follows:
•
To increase air mixture, pull down the adjustment rod located beneath the stove. This
opens the shutter more and will stop sooting. Figure 47
•
To decrease air mixture, push up the adjustment rod located beneath the stove. This
closes the shutter. Flames will be more yellow. Figure 48
Figure 47 -
Push Adjustment Rod Up to
Close Air Shutter
Figure 48 -
Pull Adjustment Rod Down
to Open Air Shutter
3
AIR SHUTTER ADjUSTmENT (NATURAL GAS ONLy)
Air Shutter
ST1149
Adjustment
Rod
ST1150
air shutter closed
Air Shutter
Adjustment
Rod
ST1150
Lg1151
air shutter open
58D6056