TROUBLE SHOOTING

7-1. How to check the parts
Parts name
Room temperature
Disconnect the connector, then measure the resistance using a tester.
thermistor
(Sorrounding temperature 10°C~30°C)
(TH21)
Liquid pipe thermistor
(TH22)
Gas pipe thermistor
(TH23)
Trans
Disconnect the connector and measure the resistance using a tester.
CNT
CN3T
3T
3
1
PEFY-P40~140
Fan motor
Relay connector
Protector
Fan motor
PEFY-P200
Protector
Linear expansion
Disconnect the connector then measure the resistance valve using a tester.
valve
CN60
White
1
Yellow
2
Orange
3
LEV
Blue
4
Red
5
Brown
6
Drain Pump
Disconnect the connector then measure the resistance
(Drain water lift up kit)
valve using a tester.
(Sorrounding temperature 20°C~30°C)
Red
1
Red
3
Drain sensor
Measure the resistance between the terminals using
(Drain water lift up kit)
a tester.
3
1
Normal
4.3k
~9.6k
Open or short
Normal
CNT(1)-(3)
App.15
CN3T(1)-(3)
App.4
Measure the resistance between the terminals using a tester.
Motor terminal
or
Gray
1
Relay connector
2
Blue
3
Gray-Orange
Black
4
Orange
5
Gray-Black
Blown
6
7
Gray-Brown
Red
8
Red
Gray-Blue
9
·
250
Measure the resistance between the terminals using a tester.
Relay connector
Motor terminal
Brown
4
or
Relay connector
Red
Red-White
1
Orange
8
Orange
White-Black
9
Red-Black
White
2
Brown-Gray
Gray
5
Black
Gray-Yellow
3
Yellow
6
Brown-Yellow
Normal
(1)-(5)
(2)-(6)
White-Red
Yellow-Brown
150Ω
Normal
399Ω
Open or short
(Refer to the thermistor characteristic graph)
0°C/6.0kΩ, 10°C/3.9kΩ
20°C/2.6kΩ, 25°C/2.2kΩ
30°C/1.8kΩ, 40°C/1.3kΩ
Check points
Abnormal
(Refer to the thermistor characteristic graph)
Abnormal
Open or short
Normal
P40· 50
P63
68.8Ω
47Ω
53.73Ω
37.29Ω
27.56Ω
59.92Ω
39.81Ω
30.64Ω
74.17Ω
49.8Ω
38.31Ω
Normal
Abnormal
5Ω
5Ω
5Ω
Open or short
6.08Ω
6.08Ω
6.08Ω
(3)-(5)
(4)-(6)
Orange-Red
Blue-Brown
±10%
Abnormal
P71
P80
P100·125·140
32.9Ω
33.3Ω
14.05Ω
27.1Ω
9.11Ω
28.56Ω
9.87Ω
36.82Ω
12.89Ω
Abnormal
Open or short
<Thermistor characteristic graph>
Room temperature thermistor(TH21)
Liquid pipe thermistor(TH22)
Gas pipe temperature thermistor(TH23)
Drain sensor(DS)
Thermistor R
=15kΩ ± 3%
0
Fixed number of B=3480kΩ ± 2%
1
Rt=15exp { 3480(
273+t
0°C
15kΩ
50
10°C 9.6kΩ
20°C 6.3kΩ
25°C 5.2kΩ
40
30°C 4.3kΩ
40°C 3.0kΩ
30
20
10
0
-20 -10 0 10 20 30 40 50
(at 20°C)
Abnormal
Open or short
(at 20°C)
1
) }
273
Temperature (°C)
14