Table 11. Settings (Continued)
Settings
Setting Option
Submenu
L2 Settings
L2 Over Current Warning Level [0.0A]...[48.0A] *
L2 Over Current Alarm Level
L2 Low Current Warning Level
L3 Settings
L3 Over Current Warning Level [0.0A]...[48.0A] *
L3 Over Current Alarm Level
L3 Low Current Warning Level
*
DELLM0001, DELLM001A, DELLM0004, DELLM004A, DELLM0006
** DELLM0002, DELLM0005, DELLM0007
*** DELLM0003
For Delta models, L1 represents L1-L3 data, L2 represents L1-L2 data, and L3 represents L2-L3 data.
NOTE:
|
46
LCD Operation
Available Settings
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading greater
than this value causes a warning to generate.
This warning indicates that the current A
reading has risen to an unacceptable level.
[0.0A]...[48.0A] *
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading greater
than this value causes a over current alarm to
generate.
[0.0A]...[48.0A] *
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading less
than this value causes a warning to generate.
This warning indicates that the current A
reading is reduced to an unacceptable level.
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading greater
than this value causes a warning to generate.
This warning indicates that the current A
reading has risen to an unacceptable level.
[0.0A]...[48.0A] *
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading greater
than this value causes an over current alarm to
generate.
[0.0A]...[48.0A] *
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading less
than this value causes a warning to generate.
This warning indicates that the current A
reading is reduced to an unacceptable level.
Default Setting
38.4A
25.6A
12.8A
48.0A
32.0A
16.0A
0.0A
0.0A
0.0A
38.4A
25.6A
12.8A
48.0A
32.0A
16.0A
0.0A
0.0A
0.0A