Model Number Nomenclature; Ari Capacities - Carrier 50JX Series Product Data

Single-packaged heat pump units 2 to 5 nominal tons
Table of Contents

Advertisement

Model number nomenclature

Model No.
50JX – Single Packaged
Heat Pump
Nominal Cooling Capacity (Tons)
024 – 2
030 – 2-1/2
036 – 3
042 – 3-1/2
048 – 4
060 – 5
AL — Aluminum
CU — Copper
ARI* capacities
UNIT
50JX
024
030
036
042
048
060
LEGEND
dB
— Sound Levels (decibels)
COP
— Coefficient of Performance
HSPF
— Heating Season Performance Factor
db
— Dry Bulb
SEER
— Seasonal Energy Efficiency Ratio
wb
— Wet Bulb
* Air Conditioning & Refrigeration Institute.
† Rated in accordance with U.S. Government DOE Department of
UNIT
HIGH HEAT CAPACITY
50JX
(BTUH)@47°F
024
030
036
042
048
060
3
50JX
024
TT
COOLING CAPACITIES AND EFFICIENCIES
NOMINAL
STANDARD
TONS
CFM
2
800
2-1/2
1000
3
1200
3-1/2
1400
4
1450
5
1750
HEATING CAPACITIES AND EFFICIENCIES
HIGH HEAT COP
@47°F
22,400
3.2
28,200
3.2
34,000
3.2
40,000
3.2
44,000
3.1
57,000
3.2
0
1
AD
Options
- - – Wire Grille
AD – Louvered Grille
Options
BT – Wire Grille and vinyl-coated
(None) – Wire Grille
outdoor coil fin
AD – Louvered Grille
XT – Louvered Grille and vinyl-coated
BT – Wire Grille and Vinyl-Coated Condenser
outdoor coil fin
Coil Fin
CC – Wire Grille, AL indoor and CU/CU
XT – Louvered Grille and Vinyl-Coated Con-
outdoor coil
denser Coil Fin
CU – Wire Grille, CU/CU indoor and
CC – Wire Grille, AL Evaporator and CU/CU
outdoor coils
Condenser Coil
AC – Louvered Grille, AL indoor and
AC – Louvered Grille, AL Evaporator and CU/
CU/CU outdoor coil
CU condenser Coil
AU – Louvered Grille, CU/CU indoor and
AU – Louvered Grille, CU/CU Evaporator and
outdoor coils
Condenser Coils
Packaging
Series
V-Ph-Hz
3 – 208/230-1-60
5 – 208/230-3-60
6 – 460-3-60
NET COOLING
CAPACITIES
(Btuh)
23,200
29,000
35,000
41,500
47,000
60,000
Energy) test procedures and/or ARI Standard 210/240-94.
‡ Tested in accordance with ARI Standard 270-95 (not listed in ARI).
NOTES:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F db, 67°F wb indoor entering-air tempera-
ture and 95°F db outdoor entering-air temperature.
2. Before purchasing this appliance, read important energy cost and
efficiency information available from your retailer.
LOW HEAT CAPACITY
(BTUH)@17°F
13,000
15,600
19,000
22,000
23,600
32,000
SOUND
SEER†
RATINGS‡
(dB)
12.0
12.0
12.0
12.0
12.0
12.0
LOW HEAT COP
HSPF
@17°F
2
2
1.9
2
2
2
72
72
77
73
79
79
7.1
7.1
7.1
7.2
7.1
7.2
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50jx02450jx03050jx03650jx04250jx04850jx060

Table of Contents