Prepare Wall Penetrations; Termination And Fittings; Multiple Vent/Air Terminations - Lochinvar 150 - 500 Installation & Operation Manual

Armor water heater
Table of Contents

Advertisement

4
Sidewall direct venting

Prepare wall penetrations

1.
Use the factory supplied wall plate as a template to locate
the vent and air intake holes and mounting holes.
Air pipe penetration:
a.
Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
Vent pipe penetration:
a.
Cut a hole for the vent pipe. For either combustible or
noncombustible construction, size the vent pipe hole
with at least a 1/2 inch clearance around the vent pipe
outer diameter:
• 4½ inch hole for 3 inch vent pipe
• 5½ inch hole for 4 inch vent pipe
Drill 3/16" diameter holes for inserting the plastic anchors
into the wall.
2.
Install the vent and air intake piping through the wall into
the vent plate openings. Seal all gaps between the pipes and
wall. Use RTV silicone sealant to seal the air pipe. Use the
cement/primer listed in Table 3A on page 15 to seal the vent
pipe.
3.
Mount and secure the vent plate to the wall using stainless
steel screws. Seal around the plate to the wall assuring no
air gaps.
4.
Assemble the vent cap to the vent plate (see FIG. 4-4A).
Insert the stainless steel screws into the vent cap screw hole
openings and securely attach the vent cap to the vent plate.
5. Seal all wall cavities.
Figure 4-4A Sidewall Termination Assembly
AIR PIPING
VENT PIPING
WALL PLATE
GALVANIZED
THIMBLE
Prepare wall penetrations (Alternate -
Field Supplied Option)
1.
Air pipe penetration:
a.
Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2.
Vent pipe penetration:
a.
Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole with at least a 1/2 inch clearance around the vent
pipe outer diameter:
• 4½ inch hole for 3 inch vent pipe
• 5½ inch hole for 4 inch vent pipe
b.
Insert a galvanized metal thimble in the vent pipe
hole as shown in FIG. 4-4B.
3. Use a sidewall termination plate as a template for correct
location of hole centers.
4. Follow all local codes for isolation of vent pipe when passing
through floors or walls.
5. Seal exterior openings thoroughly with exterior caulk.
20
Figure 4-4B Alternate Sidewall Termination Assembly
w/Field Supplied Fittings
VENT PIPING

Termination and fittings

1. The air termination coupling must be oriented at least
12 inches above grade or snow line as shown in FIG. 4-1A,
page 18.
2. Maintain the required dimensions of the finished
termination piping as shown in FIG. 4-1A, page 18.
3. If using the alternate sidewall termination do not extend
exposed vent pipe outside of the building more than what is
shown in this document. Condensate could freeze and
block vent pipe.
4. PVC/CPVC terminations are designed to accommodate any
wall thickness of standard constructions per the directions
found in this manual.

Multiple vent/air terminations

1. When terminating multiple Armor water heaters terminate
each vent/air connection as described in this manual
(FIG. 4-5A).
WARNING
VENT PLATE
VENT CAP
2. Place wall penetrations to obtain minimum clearance of
12 inches between edge of air inlet and adjacent vent outlet,
as shown in FIG. 4-5A for U.S. installations. For Canadian
installations, provide clearances required by CSA B149.1
Installation Code.
3. The air inlet of a Armor water heater is part of a direct vent
connection. It is not classified as a forced air intake with
regard to spacing from adjacent water heater vents.
Figure 4-5A Multiple Vent Terminations (must also
comply with Figure 4-1A)
Installation & Operation Manual
AIR PIPING
GALVANIZED
THIMBLE
SIDEWALL
TERMINATION PLATE
All vent pipes and air inlets must terminate
at the same height to avoid possibility of
severe personal injury, death, or substantial
property damage.
12" MIN. BETWEEN EDGE OF AIR
INLET AND ADJACENT VENT OUTLET
VENT
VENT / AIR
TERMINATION
ELBOW
BIRD SCREEN
BIRD SCREEN
ELBOW
BIRD SCREEN
AIR

Hide quick links: