Carrier BWMAAN000050 Installation, Operation And Maintenance Manual page 66

Wall mounted stainless steel condensing gas boiler
Table of Contents

Advertisement

User Interface Display
C H
S E T T I N G S
C H
m o d e
C H
w i
t h
t h e r m o s t a t ▼
APPENDIX A - CONTROL MODULE
4. Central Heating (CH) modes available:
• CH Mode = 0 'CH with Thermostat'
• CH Mode = 1 'CH with Thermostat and Outdoor Reset'
• CH Mode = 2 'CH with Full Outdoor Reset'
M O D E : 1
• CH Mode = 3 'CH with Permanent Demand'
Note:
• Once CH demand is satisfi ed (i.e. CH thermostat opens or
boiler determines its minimum fi ring rate exceeds system
heating load):
• The internal heat exchanger pump is energized anytime demand
exists regardless of Pump Mode setting or type of demand (CH or
DHW).
66
Explanation
• Boiler will attempt to satisfy CH demand while CH
thermostat input is closed.
• Boiler will modulate its fi ring rate to maintain CH set
point and match system heat load.
• CH set point adjusted in 'Settings' submenu under 'User
Menu'
• Boiler will attempt to satisfy CH demand when CH
thermostat input is closed.
• Boiler will modulate its fi ring rate to maintain CH set
point and match system heat load.
• CH set point calculated as function of outdoor
temperature using outdoor reset curve. See fi gure A-2
• Boiler will permanently attempt to satisfy CH
demand.
• CH thermostat input is ignored.
• CH set point calculated as function of outdoor
temperature using outdoor reset curve. See fi gure A-2
• Boiler will permanently attempt to satisfy CH
demand.
• CH thermostat input is ignored.
• CH set point is adjusted in 'Settings' submenu under
'User Menu'
• Burner shuts off, boiler enters post purge.
• CH pump continues to run for 30 seconds.
• Control will wait until Anti-cycle time of 180 seconds
elapses before boiler fi res again. Prevents short-
cycling.