Auto Mode On/Off Selection; Check Thermostat Operation; Heating Operation; Checklist - Carrier Non-Programmable Thermostats Installation, Start-Up, And Operating Instructions Manual

Non-programmable thermostats
Table of Contents

Advertisement

higher or lower value. The selected number is the number of
degrees, plus or minus, which will be added to the actual
temperature. The number can range between -5 and +5. Factory
default is 0. This adjusted value will be used as actual temperature
for both display and control action. For example, if 2 is selected,
72°F actual will read 74°F. If set point is 72, the room will control
to an actual value of 70 which will be displayed and acted upon as
if it were 72. The effect is that a positive number selection will
make the room temperature lower and vice versa. This thermostat
is factory calibrated within an accurancy of plus or minus 1°F, so
this adjustment will provide the best accuracy when set to 0.
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 13. This selects Option
13. The SET icon should be off.
3. Press MODE button once. The SET icon will come on. The
display now shows Option 13 setting.
4. Use up and down buttons to move between available Option
14 choices of -5 through +5 in 1° steps.
5. Press MODE button again to return to Option 13 indication of
13. The SET icon will now be off.
6. Use up and down buttons to select another Option, or press
FAN button to exit configuration mode.
OPTION 15—AUTO MODE ON/OFF SELECTION
This options allows the installer to enable or disable AUTO mode
(automatic changeover between heat and cool). When disabled,
AUTO icon does not appear when successive presses of MODE
button are used to move between OFF, HEAT, and EHEAT (in
heat pump systems). Factory default is ON (AUTO mode enabled).
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 15. This selects Option
15. The SET icon should be off.
3. Press MODE button once. The SET icon will come on. The
display now shows Option 15 setting.
4. Use up and down buttons to move between available Option
15 choices of ON or OF.
5. Press MODE button again to return to Option 15 indication of
15. The SET icon will now be off.
6. Use up and down buttons to select another Option, or press
FAN button to exit configuration mode.
Step 5—Check Thermostat Operation
FAN OPERATION
1. Press FAN button, starting fan operation. FAN icon turns on.
2. Press FAN button again, stopping fan operation. FAN icon
turns off. (Some fan coils have 90 sec fan off delay, so fan
may not stop immediately.)

HEATING OPERATION

1. Press and release MODE button until HEAT icon appears.
This selects heating mode.
2. Press and release up button until set point is at least 5° above
room temperature. Within a few seconds, HEAT ON icon will
either stay on or flash. Flashing indicates a heat demand exists,
but the cycle timer or timeguard timer is delaying heat turn on.
(See "Operational Information" on page 11 for timer explana-
tion.) To defeat timer, simultaneously press FAN and up
buttons. Heating will come on within a few seconds and
HEAT ON icon will stay on. Lowering set point to below
room temperature will turn off heating and remove HEAT ON
icon within a few seconds.
COOLING OPERATION
1. Press and release MODE button until COOL icon appears.
This selects cooling mode.
2. Press and release down button until set point is at least 5°
below room temperature. Within a few seconds, COOL ON
icon will either stay on or flash. Flashing indicates a cooling
demand exists, but cycle timer or timeguard timer is delaying
cooling turn on. (See "Operational Information" on page 11
for timer explanation.) To defeat timer, simultaneously press
FAN and up buttons. Cooling will come on within a few
seconds and COOL ON icon will stay on. Raising set point to
above room temperature will turn off cooling and remove
COOL ON icon within a few seconds.
OUTDOOR TEMPERATURE
If system is equipped with an outdoor temperature sensor, check its
operation by pressing the up and down buttons together. Outdoor
temperature will be displayed for about 5 sec. If "--" is displayed,
the outdoor temperature sensor is absent or not properly connected.
Step 6—Checklist
1. Run equipment through several heating and cooling cycles to
ensure proper operation.
2. If equipment is to be left in operation, set point and operating
mode must be properly selected.
3. Put away tools and instruments, and clean up debris.
4. Review Homeowner's Guide with owner.
5. Leave literature packet with owner.
4