WET COIL DELIVERY—HORIZONTAL AND DOWNFLOW DISCHARGE UNIT 50JZ 024-060
230 AND 460 VOLT
Unit
Motor Speed
50JZ
Watts
Low
Cfm
Watts
024
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
030
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
036
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
042
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
048
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
060
Med
Cfm
Watts
High
Cfm
*Air delivery values are based on operating voltage of 230 v or 460 v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure
drops to obtain static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling ariflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may
occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.