Choice Of Flue; Savio Heat Only Manual; Venting 9 - Savio Installation & Operation Instructions

Wall hung gas boiler for central heating supply
Table of Contents

Advertisement

9. Venting Cont.
The following ue kits are available for connecting to the boiler:
A
Standard coaxial horizontal ue kit (Exhaust & intake outside)
Figure 9.2
It can be tted to allow discharge to the rear or either side of the boiler via the anged
boiler adapter elbow. Minimum lenght required is 1 ft. Maximum equivalent lenght
of 32.8 ft can be achieved utilising extensions. This ue system can only be used to
discharge horizontally, it is not designed to enable termination in the vertical plane.
Installation:
Drill hole A (on the wall template) through the outside wall that is less than 18" thick.
Cut the pipes as necessary so that a no more than 6" protrudes from the house.
Slide the intake and exhaust pipes through the hole.
Slide one rubber wall trim piece on the pipe from inside and one from outside.
Connect exhaust (inner) pipe to concentric elbow.
Connect intake (outer) pipe to concentric elbow.
Secure elbow to boiler using gasket and four screws provided.
Secure end cap on the intake pipe outside the house.

SAVIO HEAT ONLY MANUAL

9.3
Choice of ue:
(Coaxial 2.5/4.0 inches – nominal lenght 3.3 ft)
17