Carrier AQUAZONE 50HQL072-120 Installation, Start-Up And Service Instructions Manual page 28

Water source heat pump units
Table of Contents

Advertisement

RATED
CFM
0.0
BHP
0.71
4000
RPM
600
B
Turns Open
3
BHP
0.89
4400
RPM
633
Turns Open
2
BHP
1.11
4800
RPM
670
Turns Open
1.5
BHP
1.36
5200
RPM
708
Turns Open
0.5
BHP
1.64
5600
RPM
744
Turns Open
4.5
BHP
1.95
6000
RPM
777
Turns Open
4
BHP
2.27
6400
RPM
807
Turns Open
3.5
LEGEND
A
— Standard Static Sheave/Standard Motor
B
— Low-Static Sheave/Standard Motor
C
— High-Static Sheave/Standard Motor
ARI
— Air Conditioning and Refrigeration Institute
BHP — Brake Horsepower
ESP — External Static Pressure
ISO
— International Organization for Standardization
RPM — Revolutions Per Minute
NOTES:
1. Due to alternate sheaves, 'Turns Open' may vary within ±0.5 turn from
the position shown above.
2. Units factory shipped with standard static sheave and drive at 2.5
turns open (5200 cfm at 0.4 in. wg ESP Wet Coil). Other speeds
require field selection.
RATED
CFM
0.0
BHP
5400
RPM
Turns Open
BHP
5800
RPM
Turns Open
BHP
6200
RPM
Turns Open
BHP
6600
RPM
Turns Open
BHP
7000
RPM
Turns Open
BHP
7400
RPM
Turns Open
BHP
0.82
7800
RPM
550
Turns Open
4.5
BHP
0.93
8200
RPM
570
Turns Open
4
LEGEND
A
— Standard Static Sheave/Standard Motor
B
— Low-Static Sheave/Standard Motor
E
— High-Static Sheave/Large Motor
ARI
— Air Conditioning and Refrigeration Institute
BHP — Brake Horsepower
ESP — External Static Pressure
ISO
— International Organization for Standardization
RPM — Revolutions Per Minute
NOTES:
1. Bold numbers require 2 horsepower motor.
2. Values are per blower and motor; 2 blowers and motors required.
3. Due to alternate sheaves, 'Turns Open' may vary within ±0.5 turn
from the position shown above.
4. Units factory shipped with standard static sheave and drive at 2.5
turns open (7000 cfm at 0.7 in. wg ESP Wet Coil). Other speeds
require field selection.
Table 12 — 50VQL160 Blower Performance Data
0.1
0.2
0.3
0.4
0.5
0.79
0.86
0.94
1.02
1.10
641
681
720
757
794
2
1
0.5
4.5
3.5
0.97
1.06
1.14
1.22
1.31
671
708
745
780
814
1.5
0.5
4.5
4
1.20
1.28
1.37
1.46
1.56
705
740
774
807
840
1
4.5
4
3.5
2.5
1.45
1.55
1.64
1.74
1.84
741
773
805
837
867
4.5
4
3.5
2.5
1.74
1.84
1.94
2.05
2.15
775
806
836
866
895
4
3.5
3
2
1.5
2.05
2.16
2.27
2.38
2.49
807
836
865
893
921
3.5
3
2
1.5
2.38
2.50
2.61
2.73
2.85
835
862
890
917
943
3
2.5
1.5
1
0.5
Table 13 — 50VQL200 Blower Performance Data
0.1
0.2
0.3
0.4
0.50
0.56
561
599
4.5
3.5
0.57
0.63
576
613
4
3
0.58
0.64
0.71
553
590
626
4.5
3.5
2.5
0.66
0.73
0.80
569
604
638
B
4
3
2.5
0.68
0.75
0.82
0.89
549
584
618
651
4.5
3.5
3
2
0.78
0.85
0.92
0.99
566
600
633
665
4
3.5
2.5
1.5
0.89
0.96
1.03
1.10
584
616
648
679
3.5
3
2
1.5
1.00
1.08
1.15
1.23
602
633
664
693
3.5
2.5
1.5
1
EXTERNAL STATIC PRESSURE (in. wg)
0.6
0.7
0.8
0.9
1.18
1.26
1.34
1.43
829
864
898
931
3
2
1.5
1
1.40
1.48
1.57
1.66
848
881
913
945
3
2.5
2
1.5
0.5
1.65
1.74
1.84
1.93
A
872
903
934
964
2
1.5
1
0.5
1.94
2.04
2.14
2.24
898
927
957
985
2
1.5
1
0.5
0
2.26
2.36
2.47
2.58
924
952
980
1007
1
0.5
0
3
2.60
2.71
948
975
1
0.5
0
3. ISO/ARI rating point with standard static sheave and drive at 2 turns
open (5200 cfm at 0.48 in. wg ESP Wet Coil). Other speeds require
field selection.
4. For applications requiring higher static pressures, contact your local
representative.
5. Performance data does not include drive losses and is based on sea
level conditions.
6. Do not operate in gray region.
7. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e.,
208 v for 208-230-v units.
8. For wet coil performance first calculate the face velocity of the air coil
(Face Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for veloci-
ties of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by
0.08 in. wg, 400 fpm by 0.12 in. wg and 500 fpm by 0.16 in. wg.
EXTERNAL STATIC PRESSURE (in. wg)
0.5
0.6
0.7
0.8
0.63
0.70
0.77
0.84
0.90
635
670
704
736
2.5
1.5
4.5
4
0.70
0.78
0.86
0.92
0.99
648
682
714
746
2
1
4.5
4
0.78
0.86
0.94
1.02
1.10
660
693
724
755
2
1
4.5
3.5
0.87
0.94
1.02
1.11
1.19
671
703
734
764
1.5
4.5
4
3.5
0.96
1.04
1.12
1.21
1.28
683
714
744
773
1
4.5
4
3.5
1.07
1.15
1.23
1.31
1.40
696
726
755
783
1
4
3.5
3
1.18
1.26
1.35
1.43
1.52
709
738
766
794
4.5
4
3.5
3
1.31
1.39
1.48
1.56
1.66
722
751
778
805
4.5
3.5
5
4.5
5. ISO/ARI rating point with standard static sheave and drive at 3.5
turns open (7000 cfm at 0.45 in. wg ESP Wet Coil). Other speeds
require field selection.
6. For applications requiring higher static pressures, contact your local
representative.
7. Performance data does not include drive losses and is based on
sea level conditions.
8. Do not operate in gray region.
9. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e.,
208 v for 208-230-v units.
10. For wet coil performance first calculate the face velocity of the air
coil (Face Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for
velocities of 200 fpm reduce the static capability by 0.03 in. wg,
300 fpm by 0.08 in. wg, 400 fpm by 0.12 in. wg and 500 fpm by
0.16 in. wg.
28
1.0
1.1
1.2
1.3
1.51
1.60
1.69
1.78
964
996
1027
1058
0.5
3
2.5
2
1.75
1.85
1.94
2.03
976
1006
1036
1066
0
3
2.5
2
2.03
2.13
2.23
2.33
993
1022
1051
1079
3
2.5
2
2
2.34
2.45
2.55
2.66
1013
1041
1069
1096
3
2.5
2
1.5
2.69
2.80
1034
1061
2.5
2
0.9
1.0
1.1
1.2
1.3
0.97
1.03
1.10
1.17
767
797
826
854
881
3.5
3
2
1.5
1.06
1.13
1.20
1.26
776
805
833
861
887
3
2.5
2
1.5
1.19
1.27
1.35
1.43
784
813
841
868
894
A
3
2.5
2
1.5
1.28
1.36
1.45
1.53
793
821
848
874
900
3
2.5
2
3.5
1.36
1.44
1.52
1.59
802
829
856
882
907
E
2.5
2
1.5
3
2.5
1.48
1.55
1.63
1.70
811
838
864
889
914
2.5
4
3.5
3
2.5
1.62
1.71
1.81
821
847
873
898
4
4
3.5
3
1.75
1.85
832
857
883
4
3.5
3
1.4
1.5
1.87
1.96
1088
1117
1.5
1
2.13
2.23
1095
1123
1.5
1
2.43
2.53
C
1107
1134
1.5
1
2.77
2.87
1122
1149
1
0.5
1.4
1.5
1.23
1.30
907
933
1
0.5
0
1.33
1.40
913
938
1
0.5
0
1.52
1.60
919
944
1
2.5
2
1.62
1.70
925
950
3
2.5
2
1.67
1.75
932
956
2
2
1.78
939
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquazone 50vql080-300

Table of Contents