Carrier AQUAZONE 50HQL072-120 Installation, Start-Up And Service Instructions Manual page 25

Water source heat pump units
Table of Contents

Advertisement

RATED
CFM
0.0
BHP
1800
RPM
Turns Open
BHP
0.27
2000
RPM
484
Turns Open
5.0
BHP
0.36
2200
RPM
544
Turns Open
4.0
BHP
0.49
2400
RPM
605
Turns Open
2.5
BHP
0.64
2600
RPM
667
Turns Open
1.5
BHP
0.81
2800
RPM
729
Turns Open
5.0
BHP
1.02
3000
RPM
793
Turns Open
3.5
LEGEND
— Operation Not Recommended
ARI — Air Conditioning and Refrigeration Institute
BHP — Brake Horsepower
ESP — External Static Pressure
RPM — Revolutions Per Minute
ISO — International Organization for Standardization
A
— Units with Standard Static/Standard Motor Option
B
— Units with Low-Static/Standard Motor Option
C
— Units with High-Static/Standard Motor Option
E
— Units with High-Static/Large Motor Option
NOTES:
1. Boldface requires 2 hp motor.
2. Factory shipped with standard static sheave and drive at 2.5 turns
open (2400 cfm at 0.5 in. wg ESP Wet Coil). Other speeds require
field selection.
RATED
CFM
0.0
BHP
2600
RPM
Turns Open
BHP
0.87
2800
RPM
1012
Turns Open
4.5
BHP
1.05
3000
RPM
1070
Turns Open
3.5
BHP
1.25
3200
RPM
1126
Turns Open
2.5
BHP
1.46
3400
RPM
1179
Turns Open
1.0
BHP
1.69
3600
RPM
1230
Turns Open
4.5
BHP
1.94
3800
RPM
1280
Turns Open
4.0
LEGEND
— Operation Not Recommended
ARI — Air Conditioning and Refrigeration Institute
BHP — Brake Horsepower
ESP — External Static Pressure
ISO — International Organization for Standardization
RPM — Revolutions Per Minute
A
— Units with Standard Static Sheave/Standard Motor Option
B
— Units with Low-Static Sheave/Standard Motor Option
C
— Units with High-Static Sheave/Standard Motor Option
D
— Units with Standard Static Sheave/Large 3 Hp Motor Option
E
— Units with High-Static Sheave/Large 3 Hp Motor Option
NOTES:
1. Boldface requires 3 hp motor.
2. Units factory shipped with standard static sheave and drive at
2.5 turns open (3200 cfm at 0.6 in. wg ESP). Other speeds require
field selection. ISO/ARI rating point with standard static sheave and
Table 6 — 50HQL072 Blower Performance Data
0.1
0.2
0.3
0.4
0.23
0.26
0.31
0.35
482
536
587
636
B
5.0
4.0
3.0
2.0
0.31
0.35
0.40
0.44
534
582
629
674
4.0
3.0
2.0
1.5
0.41
0.46
0.51
0.56
589
633
676
717
3.0
2.0
1.5
5.0
0.54
0.59
0.64
0.70
647
687
726
765
2.0
1.0
5.0
4.0
0.69
0.75
0.81
0.86
705
742
779
814
1.0
4.5
4.0
3.0
0.87
0.93
1.00
1.06
764
799
833
866
4.0
3.5
3.0
2.0
1.09
1.15
1.22
1.29
825
858
889
920
3.0
2.5
1.5
1.0
Table 7 — 50HQL096 Blower Performance Data
0.1
0.2
0.3
0.4
0.84
0.91
0.97
1048
1095
1140
4.0
3.0
2.0
0.94
1.01
1.08
1.15
1058
1104
1148
1191
B
3.5
2.5
2.0
1.0
1.12
1.20
1.27
1.35
1114
1157
1199
1239
2.5
1.5
0.5
4.5
1.32
1.40
1.48
1.56
1167
1208
1248
1287
1.5
0.5
4.5
3.5
1.54
1.62
1.71
1.79
1219
1257
1296
1333
0.5
4.5
3.5
3.0
1.78
1.87
1.95
2.04
1268
1305
1341
1377
4.0
3.5
3.0
2.0
2.03
2.13
2.22
2.31
1316
1351
1387
1421
3.0
2.5
2.0
1.5
EXTERNAL STATIC PRESSURE (in. wg)
0.5
0.6
0.7
0.8
0.39
0.44
0.48
0.53
0.58
683
729
773
816
1.0
5.0
4.0
3.0
0.49
0.54
0.59
0.64
0.69
717
760
801
841
5.0
4.0
3.5
2.5
0.61
0.66
0.72
0.77
0.83
758
797
836
873
A
4.0
3.5
3.0
2.0
0.75
0.81
0.87
0.93
0.99
802
839
875
910
3.5
2.5
2.0
1.5
0.92
0.99
1.05
1.11
1.17
849
884
917
950
2.5
2.0
1.0
0.5
1.12
1.19
1.25
1.32
1.39
899
931
962
993
1024
1.5
1.0
0.5
0.0
1.35
1.42
1.49
1.56
1.64
951
981
1011
1040
1069
0.5
0.0
3.5
3.5
3. ISO/ARI rating point with standard static sheave and drive at
3.5 turns open (2400 cfm at 0.5 in. wg ESP Wet Coil). Other
speeds require field selection.
4. For applications requiring higher static pressures, contact your local
representative.
5. Based on 12x11 blower.
6. Performance data does not include drive losses and is based on
sea level conditions.
7. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e.,
208 V for 208-230 V units.
8. For wet coil performance first calculate the face velocity of the air
coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for
velocities of 200 fpm reduce the static capability by 0.03 in. wg,
300 fpm by 0.08 in. wg, 400 fpm by 0.12 in. wg and 500 fpm by
0.16 in. wg.
9. Large motor size is 2 hp for 50HQL072.
EXTERNAL STATIC PRESSURE (in. wg)
0.5
0.6
0.7
0.8
1.04
1.10
1.17
1.24
1184
1226
1267
1308
1.0
0.0
4.0
3.5
1.22
1.29
1.36
1.43
1232
1273
1313
1351
A
4.5
4.0
3.5
2.5
1.42
1.50
1.57
1.65
1280
1319
1356
1394
4.0
3.0
2.5
2.0
1.64
1.72
1.80
1.88
1325
1362
1400
1435
2.0
1.0
3.0
2.5
1.88
1.96
2.05
2.13
1369
1406
1441
1475
D
2.5
1.5
1.0
0.5
2.13
2.22
2.31
2.40
1413
1447
1481
1515
1.5
1.0
0.5
0.0
2.41
2.50
2.59
2.69
1455
1488
1521
1553
1.0
0.5
4.0
3.5
drive at 3.5 turns open (3200 cfm at 0.4 in. wg ESP). Other speeds
require field selection.
3. For applications requiring higher static pressures, contact your local
representative.
4. Based on 2-10x10 blowers.
5. Performance data does not include drive losses and is based on
sea level conditions.
6. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e.,
208V for 208-230V units.
7. For wet coil performance first calculate the face velocity of the air
coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for
velocities of 200 fpm reduce the static capability by 0.03 in. wg,
300 fpm by 0.08 in. wg, 400 fpm by 0.12 in. wg and 500 fpm by
0.16 in. wg.
8. Large motor size is 3 hp for 50HQL096.
25
0.9
1.0
1.1
1.2
0.63
0.68
0.73
858
899
938
977
2.5
1.5
1.0
0.0
0.75
0.80
0.86
881
919
956
993
2.0
1.0
0.5
4.0
0.88
0.94
1.00
910
946
982
1016
1.5
0.5
0.0
3.5
1.05
1.11
1.17
945
979
1012
1045
0.5
0.0
3.5
3.0
1.24
1.30
1.37
983
1015
1046
1078
0.0
3.5
3.0
2.5
1.46
1.52
1.60
1054
1084
1114
E
3.5
3.0
2.5
2.0
1.71
1.78
1.85
1098
1126
1154
3.0
2.5
2.0
1.5
0.9
1.0
1.1
1.2
1.31
1.37
1.44
1.51
1346
1384
1421
1457
2.5
2.0
1.5
1.0
1.51
1.58
1.65
1.73
1389
1426
1461
1497
2.0
1.5
1.0
4.5
1.73
1.80
1.88
1.96
1430
1465
1501
1534
1.5
0.5
0.0
4.0
2.00
2.04
2.13
2.21
1470
1505
1538
1571
0.5
0.0
4.0
3.5
2.22
2.31
2.39
2.48
1510
1543
1576
1608
E
0.0
4.0
3.5
3.0
2.49
2.58
2.67
2.76
1548
1580
1612
1643
4.0
3.5
3.0
2.5
2.78
2.88
2.97
1586
1617
1648
3.0
3.0
2.5
1.3
1.4
1.5
0.79
0.84
0.90
1015
1052
1088
3.5
3.0
2.5
0.91
0.97
1.03
1029
1064
1098
C
3.5
3.0
2.5
1.06
1.12
1.18
1050
1084
1116
3.0
2.5
2.0
1.24
1.30
1.37
1077
1109
1140
3.0
2.5
2.0
1.44
1.51
1.57
1108
1138
1168
2.5
2.0
1.5
1.67
1.74
1.81
1143
1171
1199
2.0
1.5
1.0
1.93
1182
1.0
1.3
1.4
1.5
1.58
1.65
1.72
1493
1527
1560
C
4.5
4.0
3.5
1.80
1.87
1.95
1531
1564
1597
4.0
3.5
3.0
2.04
2.12
2.20
1568
1601
1632
3.5
3.0
2.5
2.29
2.38
2.46
1604
1636
1667
3.0
2.5
2.0
2.57
2.65
2.74
1639
1671
1702
2.5
2.0
1.5
2.85
2.94
1674
1705
2.0
1.5