POINT NAME
Space Temperature Sensor
Supply Air Temperature
Local Outside Air Temperature Sensor
Space Temperature Offset Pot
Indoor Air Quality
Outdoor Air Quality
Safety Chain Feedback
Compressor Safety
Fire Shutdown
Enthalpy Switch
Humidistat Input Status
Space Relative Humidity
Outside Air Relative Humidity
Supply Fan Status
Filter Status
Remote Occupancy Input
Economizer Commanded Position
Supply Fan Relay State
Compressor 1 Relay State
Compressor 2 Relay State
Heat Stage 1 Relay State
Heat Stage 2 Relay State
Power Exhaust Relay State
Dehumidification Relay State
LEGEND
AI
--- Analog Input
AO --- Analog Output
DI
--- Discrete Input
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field --- installation.
The RTU Open controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP- - equipped 50HCQ unit, the unit is supplied with
a supply- - air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6- - inches (12.7
mm) in length. It is a nominal 10- - k ohm thermistor.
The SAT is factory- - wired. The SAT probe is wire- - tied to
the supply- - air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re- - position the sensor in the flange of the supply- - air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/
2
Use two field- - supplied, self- - drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 34.
Table 7 – RTU Open Controller Inputs and Outputs
BACnet OBJECT
NAME
sptsens
sat
oatsens
sptopot
iaq
oaq
safety
compstat
firedown
enthalpy
humstat
CONFIGURABLE INPUTS*
sprh
oarh
fanstat
filtstat
remocc
econocmd
sf
comp_1
comp_2
heat_1
heat_2
aux_2
humizer
- - in. hole in the flange or duct.
TYPE OF I/O
INPUTS
AI (10K Thermistor)
AI (10K Thermistor)
AI (10K Thermistor)
AI (100K Potentiometer)
AI (4---20 ma)
AI (4---20 ma)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
AI (4---20 ma)
AI (4---20 ma)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
OUTPUTS
4---20ma
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC, 1A)
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory- - mounted in the EconoMi$er2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$er2 —
The RTU Open control is used with EconoMi$er2 (option
or accessory) for outdoor air management. The damper
position is controlled directly by the RTU Open control;
EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with
field- - installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
sensor
2
Outdoor air CO
2
29
CONNECTION PIN
NUMBERS
J20---1, 2
J2---1, 2
J2---3, 4
J20---3
J4---2, 3
J4---5, 6
J1---9
J1---2
J1---10
J2---6, 7
J5---7, 8
J4---2,3 or J4---5,6
J5---1,2 or J5---3,4 or
J5 5,6 or J5---7,8
J2---5
J1---4
J1---8
J1---7
J1---6
J1---5
J11---3
J11---7, 8
sensor