OPERATING
UNIT SIZE
WEIGHT
50EJQ
(lb)
024
4168
028
4168
Fig. 2 — Base Unit Dimensions, 50EJQ024 and 028
CORNER WEIGHT
A
B
(lb)
ft-in.
ft-in.
1
2
5-7
3
3-7
5
843
859
8
8
5-7
3-7
843
859
3
5
8
8
3
NOTES:
1. Weights include economizer (Std)
2.
Center of gravity.
3. Do not locate adjacent units with dis-
charge facing economizer inlet. Mini-
mum clearances to be:
Adjacent Units: 15 -0
Top of Units: No overhang
Outdoor Coil: 4 -0
Economizer Side: 6 -0
Filter Access Side: 10 -0 (for re-
moval of evaporator coil)
4. For smaller service and operational
clearances, contact Carrier Applica-
tion Engineering department.
5. Bottom ducts designed to be attached
to accessory roof curb. If unit is mounted
on dunnage, it is recommended the
ducts be supported by cross braces as
done on accessory roof curb.
6. Dimensions are in inches. Dimen-
sions in [ ] are in millimeters.
7. For units with electric heat, a field-
supplied 90° elbow must be installed
in the supply ductwork below the unit
discharge.
3
4
1245
1222
1245
1222