Idc10 Alarm Port - Sentry PTPD-V0 Installation And Operation Manual

Ac power distribution unit
Table of Contents

Advertisement

IDC10 alarm port

Sentry Power Distribution Units are equipped standard with an IDC10 alarm port for use with contact-
closure overload alarm circuits. (Pins 1-7 are not used.)
Pin
8
Normally Open
9
Common
10
Normally Closed
NOTE:
1. Normally Open:
The relay switches to close the circuit in response to an over-threshold alarm.
Normally Closed: The relay switches to open the circuit in response to an over-threshold alarm.
2. Relay specifications:
Manufacturer's rating
• Maximum switching voltage – 220V DC, 250V AC
• Maximum switching current – 2A DC, AC
UL/CSA rating
• 0.6A, 125V AC
• 0.6A, 110V DC
• 2A, 20V DC
Sentry Power Tower Power Distribution Unit