Appendix A: Resetting to Factory Defaults

You may reset the non-volatile RAM that stores all configurable Sentry Power Distribution Unit
options. This clears all editable fields on the Control Screen.
You may reset the Sentry Power Distribution Unit to factory defaults by pressing the reset button.

To reset the PTPD to factory defaults using the reset button:

On the front of the PTPD, locate the recessed reset button directly below the Input Current LED. You
will need a non-conductive, non-metallic tool that fits inside the recess.
Insert the tool in the recess, then depress and hold the reset button for at least 8 seconds. A reset is
indicated by three side-by-side pairs of horizontal lines in the top, middle and bottom of the display. At
this point, you may release the reset button. The PTPD will perform a power up self-test and then
return to displaying the cumulative input load on the Input Current LED.
14 • Appendices
Sentry Power Tower Power Distribution Unit
Resetting to Factory Defaults
Installation and Operations Manual