Connecting Devices to the PTPD

To avoid the possibility of noise due to arcing:
Keep the device's on/off switch in the off position until after it is plugged into the PTPD port.
On 115V units, connect devices to the PTPD ports.
On 230V units, install a retention clip on each port. Pull the open prongs out slightly and insert them
into holes on the sides of the PTPD adjacent to the port. Then insert the device's power cord and gently
snap the retention clip over the cord.
NOTE:
1.
Server Technology recommends even distribution of attached devices across the all available outlets to avoid
exceeding the outlet, quad or octet ratings limitations. See Ratings in Appendix B: for more information.
2.
The outlet retention clips on the 230V PTPD are designed for use with Server Technology's IEC 60320/C13 to IEC
60320/C14 cable (CAB-1302). The retention clip may not properly fit 3
Always disconnect the power supply cord before opening to avoid electrical shock.
Afin d'éviter les chocs électriques, débranchez le cable électrique avant d'ouvrir.
Immer Netzleitung auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.

Connecting to the PTPD (PTPD-x0 models only)

The Sentry Power Distribution Unit is equipped with a single RJ45 RS-232 serial port for attachment to
a PC or networked terminal server using the supplied RJ45 to RJ45 crossover cable and RJ45 to DB9F
serial port adapter as required. Additionally, the PTPD is equipped with a single IDC10 alarm port for
connection to contact-closure overload alarm circuits. See Chapter 4: Appendices for more
information these ports.
Sentry Power Tower Power Distribution Unit
Installation and Operations Manual
rd
party cables.
Installation