5-3. RAS-18NKP-E / RAS-18NA-E

0.39 m
(Connecting pipe)
∅12.7
O.D.:12.7 mm
P
Packed valve
(∅12.7)
Compressor
PH340X3C-4KT1
50 Hz
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Indoor unit
Evaporator
Cross flow fan
Condenser
Propeller fan
Outdoor unit
Standard
Surface temp. of heat
pressure P
exchanger interchanging
(MPaG)
pipe T (°C)
0.41
0.56
0.32
– 16 –
FILE NO. SVM-06004
T
Packed valve
(∅6.35)
Capillary tube
∅2.0x600 s
Refrigerant
R22 1.0 kg
Mark (
) means check points of Gas Leak
Fan speed
(indoor)
11.0
High
15.0
High
2.0
Low
0.49 m
(Connecting pipe)
∅6.35
O.D.:6.35 mm
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
27/19
35/24
32/23
43/26
21/15
21/15