Hitachi RAS-S13CYT Installation Manual page 2

Split-unit air conditioner
Hide thumbs Also See for RAS-S13CYT:

Advertisement

Please mount the outdoor unit on stable ground to prevent
vibration and increase of noise level.
Decide the location for piping after sorting out the different
types of pipe available.
Open the side plate by unscrewing the screws as shown below.
Please face this side (suction
side) of the unit to the wall.
Please remove side cover
when connecting the piping
and connecting cord.
Pull downward
CAUTION
Please make sure to remove all spacers inside the unit.
Open the Top, Back and Side cover of the unit.
Pull out the spacers inside.
(Spacers are only for transportation purpose).
If not remove, vibration and noise will occur.
Top cover
Back cover
Side cover
WARNING
THIS APPLIANCE MUST BE EARTHED.
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or
could not reach the specified capacity.
Procedures of Wiring
Connect the electrical wiring between the indoor and outdoor unit as shown in below Fig.
Never connect the wiring by mistake.
The connection cord must be fixed by the band which is located on the electrical box.
Terminal Board
A
B
(L) Brown
(N) Blue
Green &
Yellow
Line Cord
Indoor Unit
30mm
GRN + YEL
Indoor
Unit
10mm
30mm
70mm
GRN + YEL
10mm
Outdoor
10mm
Unit
35mm
WARNING
The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try
to pull the individual wire to check if the contact is tight. Improper insertion may burn the
terminal.
Be sure to use only power cables approved from the authorities in your country. For example
in Germany: Cable type: NYM 3x1.5mm
2
, (fuse = 20A time delay)
Please refer to the installation manual for wire connection to the terminals of the units. The
cabling must meet the standards of electrical installation.
There is a AC voltage of 220V between the L and N terminals. Therefore, before servicing,
be sure to remove the plug from the AC outlet or switch off the main switch.
1
Insulation And Maintenance Of Pipe Connection
The connected terminals should be completed sealed with heat
insulator and then tied up with rubber strap.
Please tie the pipe and power line together with vinyl tape as shown
in the figure showing the installation of indoor and outdoor units.
Then fix their position with holders.
To enchance the heat insulation and to prevent water condensation,
please cover the outdoor part of the drain hose and pipe with insulation
pipe.
Completely seal any gap with putty.
Sleeve of
Insulation material for pipe connection
protection pipe
Putty
3
Power Source And Operation Test
Power Source
CAUTION
Please use a new socket. Accident may occur due to the use of
old socket because of poor contact.
Please plug in and then remove the plug for 2 – 3 times. This is
to ensure that the plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the
plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
<
>
IA547: A
1
Preparation of Pipe
Use a pipe cutter to cut the copper pipe.
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
Before flaring, please put on the flare nut.
Die
Outer
Diameter (ø)
6.35 (1/4")
12.7 (1/2")
2
Pipe Connection
Please be careful when bending the copper pipe.
Applied frozen grease to the connection points and then screw in manually. After that,
use a torque wrench to tighten the connection.
Flare nut
Small diameter
Torque
Wrench
wrench
Terminal Board
A
B
Green & Yellow
Outdoor Unit
Detail of cutting the connecting cord
To remove the connecting wires
for the indoor unit, please remove
the low cover panel in front of
the unit.
2
Installation Of Remote Controller
The remote controller can be placed in its holder which is fixed on wall
or beam.
To operate the remote controller at its holder, please ensure that the
unit can receive signal transmitted from the controller at the place
where the holder is to be fixed. The unit will beep when signal is
received from the remote controller. The signal transmission is weaken
by the florescent light. Therefore, during the installation of the remote
control holder, please switch on the light, even during day time, to
determine the mounting location of the holder.
The controller should be
insert from top into bottom
side of the holder as shown
in figure below.
Operation Test
Please ensure that the air conditioner is in normal operating condition
during the operation test.
Explain to your customer the proper operation procedures as
described in the user's manual.
Trimming tool
Copper pipe
CAUTION
Die
A
Copper pipe
A (mm)
Imperial flaring tool
Rigid flaring tool
0.8 – 1.5
0 – 0.5
1.0 – 2.0
0 – 1.0
Outer
Torque N.m
diameter
(kgf
cm)
of pipe
13.7 – 18.6 (140 – 190)
6.35 (1/4")
side
Big diameter
12.7 (1/2")
44.1 – 53.8 (450 – 550)
side
Valve head cap
19.6 – 24.5 (200 – 250)
Valve core cap
12.3 – 15.7 (125 – 160)
Wiring Of The Indoor Unit
For wire connection of the Indoor unit, you need to remove front panel and electrical cover.
Method to remove front panel
Refer to "How to Remove The Front Cover".
Method to remove the low cover
1
2
Pull the cover at
and
in the directions as shown by arrows to
remove the cover.
Wiring Of The Outdoor Unit
Please remove the side cover for wire connection.
You may not be able to close the side cover due to the
connecting cord, under such situation, please press against
the wall of side cover to fix it.
WARNING
Be sure that the hooks (2 places) are plugged in.
Otherwise, water leakage may occur and this causes short
circuit or faults.
Checking for the electric source and the
voltage range
Before installation, the power source must be checked and necessary wiring work
must be completed. To make the proper wiring capacity, use the wire gauges list
below for the lead-in from a pole transformer and for the wiring from a switch
board of fuse box to the outlet in consideration of the locked rotor current.
IMPORTANT
Wire length
Wire gauge
up to 16m
1.6mm (B.S. 14)
up to 10m
2.0mm (B.S. 12)
Note:
up to 15m
2.6mm (B.S. 10)
Outdoor supply cords shall not be
up to 25m
3.2mm (B.S. 18)
lighter than polychloroprene sheathed
2
up to 42m
14mm
(B.S. 16)
flexible cord, 60245 IEC 57.
How to Remove The Front Cover
1 Remove the front panel.
Please remove and attach the front panel by
both hands.
After opening the front panel by both hands.
1 1 1 1 1
Undo the right arm while pushing it inside.
2 2 2 2 2
Slide the front panel to right as shown in figure.
Then remove while pulling it to front.
Remote
2 Remove the filters.
Controller
3 After removing two screws, pull the center of
Screw (2 pieces)
the front cover towards you and release the
claws.
4 Pull the side faces (lower sections) of the front
Holder for
cover towards you as shown in the figure and
Remote Controller
remove the cover.
3
Removal Of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap
of valve core. Then, connect the charge
hose. Remove the cap of valve head.
1
Connect the vacuum pump adapter to
the vacuum pump and connect the
charge hose to the adapter.
Fully tighten the "Hi" shuttle of the
manifold valve and completely unscrew
the "Lo" shuttle. Run the vacuum pump
2
for about 10–15 minutes, then completely
tighten the "Lo" shuttle and switch off
the vacuum pump.
Completely unscrew the spindle of the
service valve (at 2 places) in anti-
3
clockwise direction to allow the flow of
coolant (using Hexagonal Wrench key).
Remove the charge hose and tighten the
cap of valve head. Check the cap's
4
periphery if there is any gas leakage.
The task is then completed.
Gas Leakage Inspection
Please use gas leakage detector to check if leakage
occurs at the connection of Flare nut as shown on
the right.
If gas leakage occurs, further tighten the connection
to stop leakage.
In case of removing Flare nut of a cooling unit, first remove a nut of
CAUTION
small diameter side, or else seal cap of big diameter side will fly out.
Connect the
earth cord
After remove the
screw and band,
put the connecting
cords and fix the
band with screw.
Investigate the power supply capacity and other electrical
conditions at the installation location.
Depending on the model of room air conditioner to be installed,
request the customer to make arrangements for the necessary
electrical work etc.
The electrical work includes the wiring work up the outlet. In
localities where electrical conditions are poor, use of a voltage
regulation is recommended.
CAUTION
IMPORTANT
Fuse Capacity
20A time delay fuse
How to Attach the Front Cover
1
Check that the drain pan is securely attached.
2
After installing the front cover onto the unit, hook
three claws at upper side of the cover securely.
Then, push the center of the front cover to lock the
claws.
3
Tighten the two screws.
4
Install the filter.
5
Slide the shafts of the right and left arms on the
washable panel along the steps to insert the shafts
into the holes till they stop. After checking that the
shafts are securely inserted, close the panel.
When the meter reaches - 101KPa
(-76cmHg) during pumping, fully
tighten the shuttle.
Meter showing pressure
Closed
Lo
Hi
Manifold valve
Charge hose
Valve
Vacuum
Valve
pump
Vacuum pump
adapter
When pumping starts, slightly loosen the
flare nut to check of air sucked in. Then
tighten the flare nut.
The body of
service valve
Cap of
valve core
Hexagonal
Wrench Key
Cap of valve head
Cap of valve head
A
B
A
B
Earth terminal
Shaft
Hole
Step

Advertisement

loading