Alternate Electrical And Gas Line Connections; Drain Pan; Freeze Protection; Furnace Suspension - Amana AMH95 Installation Instructions Manual

Gas-fired warm air furnace
Hide thumbs Also See for AMH95:
Table of Contents

Advertisement

Recommended Installation Positions
NOTE: Alternate "vertical" piping connections can not be used when
an upflow furnace is installed with supply air discharging to the
right. Use the standard flue and combustion air piping connections.
A
E
LTERNATE
LECTRICAL AND
This furnace has provisions allowing for electrical and gas line
connections through either side panel. In horizontal applications
the connections can be made either through the "top" or "bottom" of
the furnace.
D
P
RAIN
AN
A drain pan must be provided if the furnace is installed above a
conditioned area. The drain pan must cover the entire area under
the furnace (and air conditioning coil if applicable).
F
P
REEZE
ROTECTION
Refer to Section VII, Horizontal Applications and Conditions - Drain
Trap and Lines.
F
S
URNACE
USPENSION
If the furnace is installed in a crawl space it must be suspended
from the floor joist or supported by a concrete pad. Never install the
furnace on the ground or allow it to be exposed to water. Refer to
Section IV, Location Requirements and Considerations - Furnace
Suspension for further details.
G
L
C
AS
INE
ONNECTIONS
VIII. PROPANE GAS /HIGH ALTITUDE INSTALLATIONS
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF
THE CORRECT CONVERSION KITS ARE NOT INSTALLED.
MUST BE APPLIED TO INSURE SAFE AND PROPER FURNACE OPERATION.
CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE
AGENCY.
This furnace is shipped from the factory configured for natural gas
at standard altitude. Propane gas installations require an orifice
change to compensate for the energy content difference between
natural and propane gas.
High altitude installations may require both a pressure switch and
an orifice change. These changes are necessary to compensate
for the natural reduction in the density of both the gas fuel and the
combustion air at higher altitude.
For installations above 7000 feet, please refer to your distributor
for required kit(s).
HIGH ALTITUDE GAS ORIFICE CHART
Altitude
Gas
Natural
0-7000
Propane
NOTE: In Canada, gas furnaces are certified to 4500 feet.
Contact the distributor for a tabular listing of appropriate
manufacturer's kits for propane gas and/or high altitude installa-
tions. The indicated kits must be used to insure safe and proper
furnace operation. All conversions must be performed by a quali-
fied installer, or service agency.
IX. VENT/FLUE PIPE & COMBUSTION AIR PIPE
G
ENERAL
F
AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY INJURY OR
C
DEATH.
AREFULLY READ AND FOLLOW ALL INSTRUCTIONS GIVEN IN THIS
SECTION.
U
PON COMPLETION OF THE FURNACE INSTALLATION, CAREFULLY INSPECT THE
ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE THE FURNACE TO ASSURE IT
L
IS PROPERLY SEALED.
EAKS IN THE FLUE SYSTEM CAN RESULT IN SERIOUS
PERSONAL INJURY OR DEATH DUE TO EXPOSURE TO FLUE PRODUCTS,
INCLUDING CARBON MONOXIDE.
A condensing gas furnace achieves its high level of efficiency by
extracting almost all of the heat from the products of combustion
and cooling them to the point where condensation takes place.
Because of the relatively low flue gas temperature and water con-
densation requirements, PVC pipe is used as venting material.
This furnace must not be connected to Type B, BW, or L vent or vent
connector, and must not be vented into any portion of a factory built
or masonry chimney except when used as a pathway for PVC as
described later in this section. Never common vent this appliance
with another appliance or use a vent which is used by a solid fuel
appliance. Do not use commercially available "no hub connec-
tors" other than those shipped with this product.
12
WARNING
T
HE APPROPRIATE KITS
Manifold
Kit
Orifice
Pressure
None
#43
3.5" w.c.
LPT-00A
#55
10.0" w.c.
WARNING
WARNING
A
LL
Pressure
Switch
None