Volt Thermostat Wiring; 115 Volt Line Connection Of Accessories; Volt Humidifier; Gas Supply And Piping - Amana AMH95 Installation Instructions Manual

Gas-fired warm air furnace
Hide thumbs Also See for AMH95:
Table of Contents

Advertisement

24 V
T
W
OLT
HERMOSTAT
IRING
NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance.
Low voltage connections can be made through either the right or
left side panel. Thermostat wiring entrance holes are located in the
blower compartment. Wire routing must not to interfere with circu-
lator blower operation, filter removal, or routine maintenance. Re-
fer to the following figure for thermostat connections to the inte-
grated control module terminal strip.
Y
Y
W
W
Y
Y
W
W
R
R
C
R
R
G
G
G
C
C
HEATING
HEATING AND
REMOTE
ROOM
FURNACE
FURNACE
COOLING ROOM
CONDENSING
THERMOSTAT
THERMOSTAT
UNIT
Thermostat Diagram
This furnace is equipped with a 40 VA transformer to facilitate use
with most cooling equipment. Consult the wiring diagram, located
on the blower compartment door, for further details of 115 Volt and
24 Volt wiring.
115 V
L
C
A
(E
OLT
INE
ONNECTION OF
CCESSORIES
LECTRONIC
A
C
)
IR
LEANER
WARNING
T
O AVOID INJURY, ELECTRICAL SHOCK OR DEATH, DISCONNECT ELECTRICAL
POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING.
The furnace’s integrated control module is equipped with line volt-
age accessory terminals for controlling power to an optional field-
supplied electronic air cleaner.
The accessory load specifications are as follows:
Electronic Air Cleaner
1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any accessories.
Follow the air cleaner manufacturers’ instructions for locating,
mounting, grounding, and controlling these accessories. Acces-
sory wiring connections are to be made through the 1/4" quick
connect terminals provided on the furnace integrated control mod-
ule. The electronic air cleaner hot terminal is identified as EAC-H.
The electronic air cleaner neutral terminal is identified as LINE
NEUTRAL. All field wiring must conform to applicable codes. Con-
nections should be made as shown below.
OPTIONAL
ACCESSORIES
ELECTRONIC
AIR CLEANER
120 VAC
HOT AND
PARK
TERMINALS
INTEGRATED
120 VAC
CONTROL
NEUTRAL
TERMINALS
MODULE
12 PIN
CONNECTOR
Accessories Wiring
If it is necessary for the installer to supply additional line voltage
wiring to the inside of the furnace, the wiring must conform to all
local codes, and have a minimum temperature rating of 105°C. All
line voltage wire splices must be made inside the furnace junction
box.
The integrated control module electronic air cleaner terminals (EAC)
are energized with 115 volts whenever the circulator blower is en-
ergized.
24 V
H
OLT
UMIDIFIER
The yellow wire connected to the I.D. Blower pressure switch is
powered anytime the pressure switch is closed and provides 24
VAC humidifier control. Remove the yellow wire and connect the
supplied brown jumper wire to the pressure switch terminal. Re-
connect the yellow wire to the “piggyback” terminal on the brown
jumper and then connect the 24 VAC line of the humidifier to the
stripped end of the brown wire. Using a wire nut or a field-supplied
quick connect terminal can make this connection. The wiring must
conform to all local and national codes. Connect the COM side of
the humidifier to the B/C terminal on the furnace control board (or to
the COM side of the 24 VAC transformer). DO NOT CONNECT 115V
HUMIDIFIER TO THESE TERMINALS.
XII. GAS SUPPLY AND PIPING
G
ENERAL
The furnace rating plate includes the approved furnace gas input
rating and gas types. The furnace must be equipped to operate on
the type of gas applied. This includes any conversion kits required
for alternate fuels and/or high altitude.
CAUTION
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET
GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE
WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.
Inlet gas supply pressures must be maintained within the ranges
specified below. The supply pressure must be constant and avail-
able with all other household gas fired appliances operating. The
minimum gas supply pressure must be maintained to prevent
unreliable ignition. The maximum must not be exceeded to pre-
vent unit overfiring.
Inlet Gas Supply Pressure
Natural Gas
Minimum:5.0" W.C. Maximum :10.0" W.C.
Propane Gas
Minimum:11.0" W.C. Maximum :13.0" W.C.
H
A
D
IGH
LTITUDE
ERATE
When this furnace is installed at high altitude, the appropriate High
Altitude orifice kit must be applied. This is required due to the
natural reduction in the density of both the gas fuel and combus-
tion air as altitude increases. The kit will provide the proper design
certified input rate within the specified altitude range.
High altitude kits are purchased according to the installation alti-
tude and usage of either natural or propane gas. Contact your
distributor for a tabular listing of appropriate altitude ranges and
corresponding manufacturer’s high altitude (Natural, Propane Gas,
and/or Pressure Switch) kits.
Do not derate the furnace by adjusting the manifold pressure to a
lower pressure than specified on the furnace rating plate. The
combination of the lower air density and a lower manifold pressure
will prohibit the burner orifice from drawing the proper amount of
air into the burner. This may cause incomplete combustion, flash-
back, and possible yellow tipping.
Page 22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents