Typical Installation - Lennox Hearth Products Adagio-MN Dimensions And Specifications

Adagio series direct vent fireplace heaters
Hide thumbs Also See for Adagio-MN:

Advertisement

ADAGIO™-MN / ADAGIO-MP / ADAGIO-EN
Input (BTU) - Millivolt Models
Natural (NG) & Propane (LP) Gas
Models
Fuel
Input Rate (BTU / HR)
Adagio-MN
NG
13,000 (10,000 Low)
Adagio-MP
LP
13,000 (10,000 Low)
Input (BTU) - Electronic Models
Natural (NG) & Propane (LP) Gas
Models
Fuel
Input Rate (BTU / HR)
Adagio-EN
NG
13,000 (10,000 Low)
Adagio-EP
LP
13,000 (10,000 Low)
if field converted
Combustible Shelf Height - Inches (millimeters)
Models
Top Vent - with One 90 Degree Elbow
Adagio-MN
Secure Vent
Adagio-MP
*52 (1321)
Adagio-EN
* Includes 4" clearance to combustibles (required above vent components)
Minimum Clearances
Inches (millimeters)
Back
1/2 (13) - 0 (0) Spacers
Sides
1/2 (13) - 0 (0) Spacers**
Top Spacers
0 (0)
Floor
0 (0)***
Bottom of Appliance
64 (1626)
To Ceiling
Vent
3 (76) Top * - 1 (25.4)
Sides & Bottom
Service Clearances -Feet (meters)
Front
3 ft. (0.9 m)
* Note: 3 in. (75 mm) above any horizontal vent component, except for installations which have and elbow connected to fireplace collar and that ends
in a horizontal termination (this installation requires a 4" clearance above vent).
** Note: See Installation Instructions Manual on Page 6 (Step 1) for clearance requirements to the nailing flange located at each side of the unit and
any screw heads adjacent to it.
***Note: To ensure proper fit of the facade, the appliance base will need to be elevated 3/4" above the floor to allow for the proper fit of the facade (i.e.
Use 3/4" board as platform).
Typical
Installation
Printed in U.S.A. © 2007 Lennox Hearth Products
P/N 775,617M REV. A 06/2008
Tested to ANSI Z21.88 (in
Canada, CSA-2.33), and
CAN/CGA-2.17-M91 in both
USA and Canada, as vented
gas fireplace heaters.
US
Report No. 116-F-48-5
Secure Flex (flex elbow)
*53-3/4 (1365)
Side Wall Clearances (top view)
2" (51) Minimum
Clearance to Combustibles
Combustible Materials Allowed
In Shaded Area "Safe Zone"
12" (305)
5"
°
45
(127)
17"
(432)
inches (millimeters)
Min. Distance
8-1/4" (210) to
Protected Side Wall
Side
Wall
Side
Wall
Min. Distance to
14" (356)
Unprotected Side Wall
Vertical
Termination Cap
SV4.5CGV-1
(rated for high
winds and freez-
ing conditions)
* Ceiling Firestop/
Spacer (SV4.5VF)
Ceiling Framing
10-1/2 in.
(267 mm)
10-1/2 in.
(267 mm)
Do not insulate the
space between the
appliance and the
area above it.
Header
Drywall
*Shelf Height
Top Spacers
(see table)
Shelf Above Fireplace - Top Vent
Mantel Clearances
16
(406)
Top View Of
14
Fireplace
(356)
12
(305)
10
(254)
Square Horizontal Termination (SV4.5HT-2)
Firestop / spacer (SV4.5HF) shown on the exterior side
of the wall. It may also be installed on the interior side.
7"
(178)
12-1/8"
10-1/2"
(308 mm)
(267mm)
5-1/8"
(130 mm)
Adapter SV4.5RCH
Note: Center line of
Vent Piping is NOT
6 to 48 inch Vent
the Same as the
Section, Telescopic
Center line of the
vent section, Elbow or
Framed Opening.
Appliance Collar
Specifications and clearances are subject to change without notice.
Refer to Installation Manual before installation of these appliances for
updated dimensions and instructions.
4"
(102mm)
u
4" clearance is
required above the
elbow for installations
that require an elbow at
the top of the unit and
that ends in a horizontal
termination.
Inches (mm)
12 (305) Mantel
10 (254) Mantel
8 (203) Mantel
6 (152) Mantel
4 (102) Mantel
Top Of
Appliance
2 (51) Mantel
8
(203)
6
(152)
(76 mm)
1"
(25.4 mm)
See Page 1 for Min.
Distance to Base of Appliance.
Page 2 of 2
3"

Advertisement

loading

This manual is also suitable for:

Adagio-mpAdagio-en