Important Safety Information; Pre-Installation & Preparation Guidelines - WLee OUTDOOR FIREPIT FOR PROPANE AND NATURAL GAS Owner's Manual

Outdoor firepit for propane and natural gas
Table of Contents

Advertisement

PRE-INSTALLATION AND PREPARATION SAFETY GUIDELINES
A.
Before installing this outdoor campfire, check "Minimum Clearance to Combustibles" on page 2. MINIMUM
CLEARANCES must be maintained when you install this outdoor campfire. THERE MUST BE AT LEAST 60"
from the center of the burner to any combustible sidewall. The unit MUST NOT BE installed under any type of
ceiling or overhang.
B.
The outdoor campfire is for outdoor use only. DO NOT install or use this appliance inside a building, garage, or
any other enclosed area including recreational vehicles and/or boats. This unit must be installed in such a
manner that proper air ventilation is maintained without obstruction at all times, and during all weather
conditions.
C.
CHECK GAS TYPE (natural gas or propane): The gas supply you intend to use may not be the same as that
stated on your outdoor campfire rating plate. THIS CAMPFIRE IS CONSTRUCTED FOR USE WITH PROPANE
GAS. If the gas supply is different, or or you wish to change to natural gas, you MUST have the campfire
converted (method described on page 8) to the gas type you intend to use, by a qualified, professional
installer. If you are unsure, contact your dealer for assistance.
D.
DO NOT USE IF GAS PRESSURE IS LOWER THAN THE MINIMUM REQUIREMENT OR EXCEEDS THE
MAXIMUM.
E.
FOR NATURAL GAS: The minimum inlet gas supply pressure for purposes of input adjustment is 5 inches
water column and maximum inlet gas supply pressure is 10 inches water column.
FOR PROPANE: The minimum inlet gas supply pressure for purposes of input adjustment is 8 inches water
column and the maximum inlet gas supply pressure is 13 inches water column.
DO NOT INSTALL THIS UNIT IF MINIMUM PRESSURE IS NOT AVAILABLE OR IF MAXIMUM PRESSURE IS
EXCEEDED.
F.
Gas piping system must be sized to provide minimum inlet pressure at the maximum flow rate (BTU/hr). Undue
pressure loss will occur if the pipe is too small or the run is too long.
G.
For installations at elevations above 2,000 ft., contact your local dealer or gas supplier before installing as input
ratings should be reduced approximately 4% for each 1,000 ft. above sea level. Refer to the National Fuel Gas
Contact the factory for the required orifice
Code.
H.
The outdoor campfire and its main gas valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of ½ psig. This is accomplished by closing the gas
supply line valve, as required by NFPA 54, section 5-54.
I.
The outdoor campfire must be isolated from the gas supply piping system by closing its equipment shut-off valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig.
J.
INSTALLER NOTE: This unit should be installed so that it can be removed at a later date for service.
K.
GAS SUPPLY PLUMBING REQUIREMENTS
Apply only joint compounds that are resistant to all gasses on all male pipe fittings. Make sure to tighten every
joint securely. Do not use pipe joint compound to connect flare fittings.
SAFETY NOTE: An external on/off valve in the gas line is required for safety when your Outdoor Campfire is

IMPORTANT SAFETY INFORMATION

not in use. It also provides for convenient maintenance and repair.
.
3

Advertisement

Table of Contents
loading

Table of Contents