VAPORSTREAM
AREA-TyPE Humidifier Application
Information
The operating characteristics of AREA-TYPE steam humidifiers
should be considered when selecting humidifier capacities and
choosing mounting locations.
Steam discharge from the humidifier quickly cools and turns to vis-
ible, warm, microscopic drops or particles of water (fog) which are
lighter than air.
Should this fog contact any solid surface (columns, beams, ceiling,
pipes, etc.) before it disappears, it may collect and drip, as water.
The greater the space relative humidity, the higher and farther the
"fog" will carry and rise in the space before disappearing.
The table at right states the vertical (rise), horizontal (throw), and
width (spread) dimensions that can be expected with the AREA-
TYPE humidifiers.
To avoid steam impingement on surrounding areas, these dimen-
sions should be observed.
Note: Tank dimension "C," in figure 5-1 on page 5,
must be at least 35 mm and output should not
exceed 130 Kg/h.
Table: 6-1: Minimum Distance for Rise, Spread and Throw
Space
Space
temp.
RH
kg/h
Rise
0.5 m
30%
Spread
1.0 m
Throw
2.0 m
Rise
0.5 m
16° C
40%
Spread
1.0 m
Throw
2.0 m
Rise
0.5 m
50%
Spread
1.0 m
Throw
2.0 m
Rise
0.5 m
Spread
0.5 m
30%
Throw
1.5 m
Rise
0.5 m
40%
Spread
1.0 m
21° C
Throw
1.5 m
Rise
0.5 m
50%
Spread
1.0 m
Throw
1.5 m
6
MODEL VLC AREA-TyPE HUMIDIFIER
®
20
45
65
90
kg/h
kg/h
kg/h
1.5 m
2.0 m
2.5 m
2.5 m
1.5 m
2.0 m
2.5 m
2.5 m
3.0 m
4.0 m
4.0 m
5.0 m
1.5 m
2.0 m
2.5 m
3.0 m
1.5 m
2.0 m
2.5 m
3.0 m
3.0 m
4.0 m
4.5 m
5.0 m
1.5 m
2.0 m
2.5 m
3.0 m
2.0 m
2.0 m
2.5 m
3.0 m
3.0 m
4.0 m
4.5 m
5.0 m
1.0 m
1.5 m
2.0 m
2.0 m
1.0 m
1.5 m
2.0 m
2.0 m
2.5 m
3.0 m
3.5 m
4.0 m
1.0 m
1.5 m
2.0 m
2.0 m
1.0 m
1.5 m
2.0 m
2.0 m
2.5 m
3.5 m
4.0 m
4.0 m
1.0 m
1.5 m
2.0 m
2.0 m
1.0 m
1.5 m
2.0 m
2.0 m
2.5 m
3.5 m
4.0 m
4.5 m
Figure 6-1: Principle of Operation
Steam created in the evaporating chamber (1) flows up through the
chute (), and is distributed into the space (3) via the fan.
Steam
Chute
Heaters
110
130
kg/h
kg/h
3.0 m
3.0 m
5.5 m
3.0 m
3.0 m
5.5 m
3.0 m
3.0 m
5.5 m
2.5 m
2.5 m
4.5 m
2.5 m
2.5 m
5.0 m
2.5 m
2.5 m
5.0 m
Fan
OM-681