5. If you are connecting the stove to an old masonry
flue, be sure to have it inspected for cracks and gen-
eral condition.
6. It is recommended that no more than two (2) 90°
bends be used in the stove pipe installation. More
than two (2) 90° bends may decrease the amount of
draw and possibly cause smoke spillage.
7. A damper is not required in this installation. Remove
damper plate in the chimney or secure in the OPEN
position.
Mobile Home: Use only the following chimney and
mobile home kits.
Double Wall
Manufacturer
Connector Pipe
Selkirk Metalestos
Security
DC-2100
Oliver MacLeod
PRO-VENT
GSW
SUPER PIPE 6 SUPER CHIMNEY 21
cautiON: dO NOt open fire-door to a point where it
would be in contact with the combustible sidewall.
Optional fan - An optional heat exchange blower is
available for this wood burning appliance. To order
please see the local dealer where you purchased your
apppliance.

floor protection

installation on a concrete floor
An appliance mounted on a concrete floor does not
require floor protection.
Carpeting and any other combustible material shall not
cover Floor Protector.
If a combustible surface is applied to the concrete floor,
a clearance must be maintained equivalent to the area
reserved for the floor protector. (Fig. 1)
installation on a combustible floor
If the appliance is to be installed on a combustible floor
or a combustible floor covering, it must be installed on
a 3/8" (10 mm) thick noncombustible millboard floor
protector or durable equivalent. The pad must be in-
stalled beneath the appliance extending 18" (457 mm) in
Canada, 16" (406 mm) in the U.S. On any side equipped
with a door, and 8" (203 mm) on all other sides. In the
US, the pad must cover any horizontal chimney connec-
tor runs and extend 2" (51 mm) beyond each side.
A grouted ceramic floor-tile surface installed per local
building code considered equivalent.
4
High Temperature
Pipe
DS
Sentinal CF-3
S-2100
HT-3000
chimney
cONtact yOuR lOcal buildiNg autHORity
fOR appROvEd MEtHOdS Of iNStallatiON.
1. This appliance requires a masonry or pre-manufac-
tured chimney listed to ULC S629 (Canada) and UL
103HT (US) sized correctly.
2. If a masonry chimney is used, it is advisable to have
your chimney inspected for cracks and check the
general condition before you install your unit. Relin-
ing may be required to reduce the flue diameter to
the appropriate functional size.
3. To help ensure a good draft, the top of the chimney
should be at least 3 feet (914 mm) above the point
of penetration through the roof, and be at least 2 feet
(610 mm) higher than any point of the roof within 10
feet (3 m).
Figure 3
Chimney Heights
2' (610 mm) Higher
3' (914 mm)
Than Nearest Point of
Minimum
Roof Within 10' (3 m)
from Roof
Penetration
Minimum
Overall
Height from
Floor
15' (5 m)
ST1020
make shift compromises during installation.
Refer to chimney manufacturer's instructions.
ST1020

Mobile Home installation

ceiling height
10/08
An outside air installation kit must be purchased when
installing in a mobile home.
Follow directions in the manual for minimum clearanc-
es, hearth requirements, stove location and outside air
intake installation.
cautiON: the structural integrity of the mobile
home floor, wall and ceiling roof must be main-
tained.
WaRNiNg: The stove must be installed to the following
criteria:
4. The chim-
ney connec-
tor shall not
pass through
an attic, roof
space, closet,
concealed
space, floor,
ceiling, wall or
any partition
of combustible
construction.
5. The mini-
mum overall
height of
your chimney
should be
15 feet (5 m)
from the floor.
(Fig. 3)
6. Do not use
30005125