HP ProLiant Smart Array 256MB Quickspecs page 37

Hewlett-packard network adapter installation manual

Advertisement

System Unit
Dimensions (H x W x D)
(with bezel)
Weight (approximate)
Input Requirements
(per power supply)
BTU Rating
Power Specifications
Power Supply Output
Power
(per power supply)
System Inlet
Temperature
Relative Humidity
(non-condensing)
Altitude
DA - 12477 Worldwide QuickSpecs — Version 36 — 2/29/2008
3.38 x 17.54 x 26.01 in (8.59 x 44.54 x 66.07 cm)
Maximum
(all hard drives, power
supply, and processor
installed)
Minimum
(one hard drive, power
supply, and processor
installed)
Rated Line Voltage
Rated Input Current
Rated Input Frequency
Rated Input Power
Maximum
To review typical system power ratings use the Power Calculator which
is available via the online tool located at URL:
http://h30099.www3.hp.com/configurator/calc/Power%
20Calculator%20Catalog.xls
- Click on the system of interest. Example: DL380 G5
- Follow the instructions of the next screens.
Rated Steady-State
Power
Maximum Peak Power
Operating
Non-operating
Operating
Non-operating
Operating
Non-operating
60 lb (27.22 kg)
47.18 lb (20.41 kg)
100 - 132 VAC,
200 - 240 VAC
10A (at 100 VAC)
9A (at 120 VAC)
6.1A (at 200 VAC)
50 to 60 Hz
980W (at 100 VAC)
1035W (at 120 VAC)
1170W (at 240 VAC)
3350 BTU/hr (at 100 VAC)
3530 BTU/hr (at 120 VAC)
3990 BTU/hr (at 240 VAC)
800 W (at 100 VAC)
850 W (at 120 VAC)
1000W (qt 200-240 VAC)
800 W (at 100 VAC)
850 W (at 120 VAC)
1000W (at 200-240 VAC)
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change
is 10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed.
System performance may be reduced if
operating with a fan fault or above 30°C
(86°F).
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
10 to 90% relative humidity (Rh), 28°C
(82.4°F) maximum wet bulb temperature,
non-condensing.
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature,
non-condensing.
3050 m (10,000 ft). This value may be limited
by the type and number of options installed.
Maximum allowable altitude change rate is
457 m/min (1500 ft/min).
9144 m (30,000 ft). Maximum allowable
altitude change rate is 457 m/min (1500
ft/min).
Page 37