Honeywell F50F Product Data page 12

Duct mounted electronic air cleaner
Hide thumbs Also See for F50F:
Table of Contents

Advertisement

F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
5
BLUE
B4
RED
R3
Y2
GREEN
G1
1 INTERLOCK SWITCH.
2 SHORTING BAR.
3 AIRFLOW SWITCH DISABLE JUMPER.
4 OPTIONAL W8600F AIR CLEANER MONITOR. DRIVER
BOARD AND CABLE PROVIDED WITH W8600F.
5 NEON LIGHT.
NOTE: To reduce the risk of electric shock, this product has
a grounding type plug that has a third (grounding)
pin. This plug will only fit into a grounding type
power outlet. If the plug does not fit into the outlet,
contact a qualified electrician to install the proper
outlet. Do not change the plug in any way.
Alternatively, the electronic air cleaner can be wired with
conduit.
1. Open access door.
2. Remove and retain the (2) screws from the front of the
power box and the (2) screws from the sides of the
power box. See Fig. 18.
3. In the power box, remove and retain (2) wire nuts that
connect the line cord leads to the power box wiring.
4. Remove the power cord green lead from the green
grounding screw on the wiring compartment barrier.
5. Remove the power cord and the strain relief.
6. Install the plug (provided with the literature pack) in the
hole left by the power cord.
7. Attach conduit through a power box side knockout.
8. Wire the air cleaner directly to line voltage using wire
nuts. See Fig. 19. Secure ground connection to the
green ground screw on the wiring compartment
barrier.
9. Replace power supply cover and access door.
68-0137—5
BLACK
P3
BLACK
P4
J4
2
4
J1
4
6
5
2
Fig. 17. Internal schematic for electronic air cleaner with W8600F.
BLACK COLLECTOR
RED IONIZER
POWER
SUPPLY
BROWN
J3
P2
P1
BLACK
ORANGE
GRAY
1
VIOLET
BLACK
BLACK
W4 W2 W1 W3
3
AIRFLOW SWITCH BOARD
REMOVING COVER
FROM POWER BOX.
1
Fig. 18. Removing cover from power box.
12
TEST
BUTTON
RED
CONTACT
BOARD
BLACK
BLACK
M11975
2
3
M5676A