Download Print this page

Specifications; System Overview - Tripp Lite SM750XLNAFTA Specifications

Smart pro expandable tower ups system - nafta assembled version of smart750xl

Advertisement

brownouts and overvoltages, plus network-grade AC surge suppression
750VA / 450 watt power handling capability with full-time sine wave output offers guaranteed compatibility with networking, telecom and
other sensitive electronic devices
Large internal batteries offer runtimes of 30 minutes at half load (375VA) and 10 minutes at full load (750VA)
Runtime is expandable with the addition of optional BP36V15-2U (limit 1) or BP36V42-3U external battery packs
Automatic Voltage Regulation (AVR) circuits maintain user-selectable 100, 110, 120 or 127V nominal output over an input voltage range of
91-145V
Includes 8 fully-protected NEMA 5-15R output receptacles arranged in a single load bank that can be powered off and back on again via
software interface
PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification,
event logging and running user-defined script commands
Offers simultaneous monitoring by up to 3 directly-connected devices through included USB, DB9 and SNMP* interfaces (*requires optional
SNMPWEBCARD), or the monitoring of any number of additional UPS systems over IP with included PowerAlert monitoring software.
Communications ports support messaging of UPS and line power status, including on-battery, low-battery, power restored, AC line voltage,
DC battery voltage and remaining battery capacity
Supports timed inverter shutoff after unattended shutdown, activate self-test and UPS output power control for delayed or immediate reboot
of connected equipment
Supports Tripp Lite's WatchDog software application to restore unresponsive programs by systematically restarting applications, operating
systems and ultimately rebooting completely locked computers by momentarily switching UPS power off and back on again (requires
optional WATCHDOGSW)
15 LEDs offer continuous detailed status information of UPS operating parameters and site power quality
Hot-swappable batteries allow on-site battery replacement without powering off connected equipment
2 year warranty with up to $250,000 connected equipment insurance

Specifications

SYSTEM OVERVIEW

Voltage compatibility
100, 110, 120 or 127V AC
Frequency
60 Hz
compatibility
OUTPUT
Output VA
750
Output watts
450
Output nominal
100, 110, 120 or 127V AC
voltage
Output voltage
LINE MODE: Sine wave line voltage 120V (-12% / +5%), BATTERY MODE: Sine wave output 120V (+/-5%)
regulation
Output frequency
LINE MODE: Passes line frequency of +/-10% BATTERY MODE: Inverter output regulated to 60Hz (+/- 1Hz)
regulation
Outlet quantity / type
8 NEMA 5-15R
Customized load
Output receptacles are arranged in a single load bank configuration that can be remotely controlled via software
management
interface for delayed or immediate reboot of connected equipment
receptacles
Overload protection
Via 15A input breaker
INPUT
Maximum input amps
6.9A
Input connection
NEMA 5-15P
type
Input cord length
6 ft.
Recommended
120V 15A
Electrical Service
BATTERY
Full load runtime
10 minutes (750VA) expandable
Half load runtime
30 minutes (375VA) expandable

Advertisement

loading