Test Equipment Required; Performance Test - HP 6236A Operating And Service Manual

Triple output
Table of Contents

Advertisement

5-1
INTRODUCTION
SECTION V
MAINTENANCE
5-5
Table 5-1 lists the test equipment required to per-
form the various procedures described in this section.
5-2
Upon receipt of the power supply, the performance
test of Paragraph 5-6 can be made. This test is suitable for
incoming inspection. Section III contains a quick but less
comprehensive checkout procedure which can be used in
lieu of the performance test if desired.
5-3
If a fault is detected in the power supply while
making the performance test or during normal operation:
proceed to the troubleshooting procedure in Paragraph 5-32.
After troubleshooting and repair, repeat the performance
test to ensure that the fault has been properly corrected and
that no other faults exist. Before performing any mainte-
nance checks, turn on the power supply and allow a half-
hour warm-up.
5-4
TEST EQUIPMENT REQUIRED
5-6
PERFORMANCE TEST
5-7
The following test can be used as an incoming in-
spection check and appropriate portions of the test can be
repeated to check the operation of the instrument after
repairs. If the correct result is not obtained for a particular
check, proceed to the troubleshooting procedures of
Para~
graph 5-32.
- - CAUTION--
Before applying power to the supply, make
certain that its line voltage selector switch (S3)
is set for the line voltage to be used. (See
CA UTION notice in Paragraph 3-2 for addi-
tional information on S3.)
Table 5-1. Test Equipment Required
REQUIRED
RECOMMENDED
TYPE
CHARACTERISTICS
USE
MODEL
,
Digital
Sensitivity: 100J1V fyll scale
Measure DC voltages:
HP 3450A
Voltmeter
(min.). Input impedance:
calibration procedures
10 megohms (min.'.
Variable
Range: 90-130 Vac
Vary AC input
------
Voltage
Equipped with voltmeter
Transformer
accurate within 1 volt
Oscilloscope
Sensitivity: 100J1V/cm.
Display transient re-
HP 180A with 1821 A,
Differential input.
sponse and ripple and
and 1801 A or 1803A
noise waveforms.
plug-ins.
Repetitive
Rate: 60 Hz,
2J1sec.
Measure transient
See Figure 5-5.
Load Sw.
rise and fall time
response.
Resistive
Val ue: See Paragraph 5-11.
Power supply load
James G. Biddle
Loads
Tolerance: ±5%
resistor (fixed resistor
("Lubri-Tact"
or rheostat).
Rheostat)
Current
Value: See Paragraph 5-13.
Measure output current
Simpson Portable
Sampling
Accuracy: 1% (minimum)
Shunt, 06703.
Resistor (Shunt)
5-1