Coding Level 2
(continued)
Overview of coding addresses
Coding (factory default setting)
System design
00 :1
System type 1, 2:
1 heating circuit without mixing valve,
without DHW heating
Boiler/Burner
06:...
Maximum limit of the boiler water
temperature, defaulted by the boiler
coding card
07:1
Boiler number in multiboiler
system (only with Vitocontrol-S and
Vitotronic 100 control)
11:≠9
No access to the coding
addresses for the parameters
of the combustion controller
12:0
Special function OFF
Always reset to 12:0 if
"possible change" used.
21:0
No maintenance interval (operating
hours) selected
23:0
No time interval for burner service
selected
24:0
The service display is reset
28:0
No burner interval ignition
2E:0
KM-BUS connection of power/pump
module not recognized
2F:0
2F:0
Air bleed program/fill program disabled
Air bleed program/fill program disabled
32:0
*1
Influence of the signal "External
blocking" on circulation pumps:
All pumps in control function
*1
Generally, the burner will be blocked when signal "External blocking" is enabled.
Possible change
00 :2
System type 1, 2:
1 heating circuit without a mixing valve, with DHW heating
00 :3
System type 3, 6, 8:
1 heating circuit with mixing valve, without DHW heating
00 :4
System type 3, 6, 8:
1 heating circuit with mixing valve, with DHW heating
00 :5
System type 4, 5, 7:
1 heating circuit without mixing valve and 1 heating circuit
with mixing valve, without DHW heating
00 :6
System type 4, 5, 7:
1 heating circuit without mixing valve; 1 htg. circuit with
mixing valve, with DHW heating
06:20
Maximum limit of the boiler water temperature within the
to
ranges defaulted by the boiler coding card
06:127
07:2
Boiler number 2 to 4 in multiboiler system (only with
to
Vitocontrol-S and Vitotronic 100 control)
07:4
11:9
Access open to the coding addresses for the
parameters of the combustion controller
12:1
Special function ON:
During calibration, the control automatically sets the boiler
water temperature to max.
12:2
If automatic calibration is initiated, the boiler will not start
unless the temperature falls below 108°F / 42°C (see fault
Eb before adjusting)
21:1
The number of hours run before the burner should be
to
serviced is adjustable from 0 to 100
21:100
(each increment = 100 h)
23:1
Interval adjustable from 1 to 24 months
to
23:24
24:1
Service display (value displayed automatically)
28:1
Time interval adjustable from 1 to 24 h. The burner is
to
force-started once for 30 sec. within selected time interval
28:24
(only adjustable if coding address 82:_ has been set to 1).
2E:1
KM-BUS connection of power/pump module automatically
recognized
2F:1
Air bleed program enabled
2F:2
Fill program enabled
32:1
Influence of the signal "External blocking" on
to
circulation pumps: see the following table
32:15
Coding
41