Carrying Out Final Commissioning Tasks - Buderus Logano GA124 Conversion Instructions

Room air-independent special gas-fired boiler from natural gas to propane
Table of Contents

Advertisement

Start-up instructions
6. Turn gas valve ON/OFF switch counterclockwise to
ON position.
7. The automatic igniter must generate sparks towards
the pilot burner. The pilot flame must appear and
then ignite the main burner. If the main burner does
not ignite, close the gas valve. Disconnect heating
system from the power supply and inform your
customer service technician or LP gas company.
8. If the main burner has ignited, the gas valve must be
checked for leaks with soap solution. If no leaks are
found, continue with step 12. If leaks have been
found, switch ON/OFF switch on gas valve
clockwise to the OFF position. Disconnect heating
system from the power supply and set the
thermostat to the lowest setting.
9. Seal leaks. Repeat steps 1 and 2 (regardless of the
control in use).
Caution:
With aquasmart control continue with steps 3 and 4.
Then repeat steps 7 to 10 regardless of the control
in use.
10. Check the supply gas pressure while the boiler is
operating. The supply pressure must be between
4.7" and 10.5" W.C. for natural gas and between 11"
and 13" W.C. for propane gas. Record the measured
values in the commissioning protocol in the
installation and maintenance instructions.
Natural gas
GA124
[inch W.C.]
17
23
30
Tab. 2 Manifold pressure
11. Check manifold pressure. The nozzle pressure must
be set in accordance with the values in  Tab. 2. To
set the manifold pressure the cover ( Fig. 12) on
the gas valve must be removed. Turn the adjustment
screw clockwise to increase the pressure and
counterclockwise to reduce the pressure. This
setting must be adjusted while the boiler is
operating.
12. Record the set value in the commissioning protocol
of the installation and maintenance instructions and
screw the safety screw ( Fig. 12, page 11) into the
gas valve again.
We reserve the right to make any changes due to technical modifications.
Conversion instructions Logano GA124 special gas-fired boiler • Issue 2012/10
Propane
[inch W.C.]
3.6
8.9
3.6
9.9
3.5
9.5
1
5
4
Fig. 12 Gas valve
1 ON/OFF button (at ON position)
2 Screw plug for gas supply pressure measuring port
3 Safety screw for manifold pressure setting
4 Screw plug for manifold measuring port
5 Safety screw for pilot ignition pressure setting
4
2