Honeywell TRADELINE T7200D Installation Instructions Manual page 5

Series 2000 commercial microelectronic thermostats
Hide thumbs Also See for TRADELINE T7200D:
Table of Contents

Advertisement

Installer Setup
Number
(Press
Unoccupied
Temp key
to change)
Select
Not used.
1
a
2
Fan operation
(T7200D only).
Degree
14
temperature
display.
Intelligent Fan™
17
operation.
Keypad lockout
25
level (keypad
lockout is
enabled and
disabled by dip
switch 1 on
thermostat
back).
b
29
O/B Operation
(T7200E only).
Minimum off-
33
time for the
compressor.
Temperature
37
display
adjustment.
a
Number 2 must be set to 1 to extend fan operation.
b
Some models may not have this feature.Table 2.
T7200D,E SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTATS
Table 2. Thermostat Installer Setup Options.
Factory Setting
Display
Description
0
Conventional applica-
tions where
equipment controls
fan operation in heat
mode.
0
Temperature is
displayed in °F.
2
Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.
0
No lockout.
0
0—Energize in Cool
mode.
4
4-minute minimum
off-time for the
compressor.
0
No difference in
displayed
temperature and
actual room
temperature.
(Press
Display
1
1
0 or 1
1 or 2
1
0, 1, 2, 3
or 5
1 thru 6
5
Other Choices
or
key to change)
Description
Electric heat applications
where thermostat controls
fan operation in heat mode.
Temperature is displayed
in °C.
0—Fan only operates with
calls for heating or cooling
in Occupied and
Unoccupied modes.
1—Fan operates
continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.
1—Lockout all keys on
thermostat except system
and fan settings, temporary
setpoint; clock and day
adjustments.
2—Lockout all keys except
set Current Day/Time,
increase
and decrease
keys.
3—Lockout all keys except
Temporary Occupied, Set
Current Day/Time (for
clock, day adjustments).
1—Energize in Heat Mode.
Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor.
1—Display adjusts to 1°F
(0.6°C) higher than actual
room temperature.
2—Display adjusts to 2°F
(1.1°C) higher than actual
room temperature.
3—Display adjusts to 3°F
(1.7°C) higher than actual
room temperature.
4—Display adjusts to 1°F
(0.6°C) lower than actual
room temperature.
5—Display adjusts to 2°F
(1.1°C) lower than actual
room temperature.
6—Display adjusts to 3°F
(1.7°C) lower than actual
room temperature.
Actual
Setting
(continued)
62-0128—2