INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)

Configure Installer Setup

1. Press and release the System key.
2. Press System and Done keys simultaneously.
3. Hold keys for approximately five seconds, until the
screen changes.
4. When the display changes, release the System and
Done keys.
NOTE: See Table 4 for installer setup (ISU) numbers
and settings.
Installer System Tests
Use the Installer System Test section to test the heating,
cooling and fan. Refer to the latter portion of Table 4.
Installer
Setup
Installer Setup
Number
Name
0120
Date (Year Upper)
0130
Date (Year Lower)
0140
Date (Month)
0150
Date (Day)
0160
Schedule Options
0170
System Selection
0180
Heat Fan Operation 0
0185
Pre-occupancy
Purge Duration
0190
Reversing Valve
O/B
0220
Cycles Per Hour
(CPH) for first stage
cooling/compressor
0240
CPH for first stage
heat
0270
CPH for Em Heat
0280
Continuous
Backlight
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 4. Installer Setup Menu.
Default
Setting
All Settings
20
20—21
08
00-99
6
1-12
15
1-31 (Month Dependent)
4
0—Non-Programmable
4—Programmable
1
1—1H/1C Conv
2—1H w/o fan
3—1H with fan
4—1C
5—1H/1C HP
6—2H/1C HP
7—4 pipe Fan Coil
8—2 pipe Fan Coil
9—2 pipe Fan Coil w/ Aux
Heat
10—PTAC 1H/1C (Hi
speed, Lo speed Fan)
11—PTAC 2H/1C (Hi
speed, Lo speed Fan)
0—Fossil
1—Electric
0
0—no duration
1—one hour
2—two hours
3—three hours
0
0—O (O/B On Cool)
1—B (O/B On Heat)
3
1-6
5
1-12
9
1-12
0
0—No
1—Yes
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling
and fan. The setting chosen for System Type
(Installer Setup Number 0170) can prevent some
System Test Numbers from appearing.
Available year range: 2001 - 2178
Available year range: 2001 - 2178
Relay Y is used for 2 pipe fan coil output relay.
Only shows up if conventional system with heat
stages and fan capability is selected (ISU 0170). If
heat pump is selected, fan defaults to electric. If
fan coil or PTAC modes are selected, fan defaults
to electric (does not show up).
Shown only if system has fan and schedule is
programmable (ISU 0160).
Pre-occupancy purge is enabled by a nonzero
duration.
Only shown if heat pump or PTAC system is
selected.
Only shown if system has cool stages (ISU 0170).
Shown for heat pump, fan coil, PTAC, and
conventional cooling stages.
Only shown if system is conventional with heat
stages, 4 pipe fan coil, 2 pipe fan coil (ISU 0170).
Only shown if HP with reheat, 2 pipe fan coil with
reheat, and PTAC with reheat (ISU 0170).
Always shown; however, if AC power is not
present, the option is overridden and normal
backlight operation occurs.
9
Notes
62-0273—05