Honeywell SERIES COMMUNICATING TB7600 Installation Instructions Manual page 17

Tb7600 series communicating rtu/heat pump thermostats for commercial hvac applications
Hide thumbs Also See for SERIES COMMUNICATING TB7600:
Table of Contents

Advertisement

Configuration
parameters
Significance Default value
Resume/
Override
scheduling
Resume
Level
sched Y/N
Yes access Yes access
0
Yes access No access
1
No access
2
Pwr del
Power-up delay
Default value = 10 seconds
Frost pr
Frost protection enabled
Default value = Off
On heat pump models the system
mode will be forced to
EMERGENCY mode if frost
protection is activated
Heat max
Maximum heating setpoint limit
Default value = 90 F (32 C)
Cool min
Minimum cooling setpoint limit
Default value = 54 F (12 C)
Pband
Proportional Band setting
Default value 2 = 2.0 F (0.6 C)
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS
Table 14. Configuration Parameters for all models (Continued)
Table 15. Keypad Lock Out Levels
Permanent
Occupied
and
Temporary
Unoccupied
setpoints
Setpoints
using arrows
RoomTemp
Up key ( )
set Y/N
Down key ( )
Yes access
Yes access
No access
No access
System
mode
Fan mode
setting
setting
Sys mode
Fan mode
set Y/N
set Y/N
Yes access Yes access Yes access Yes access Yes access
No access No access No access Yes access No access
No access No access No access Yes access No access
On initial power up of the thermostat (each time 24 Vac power
supply is removed and re-applied) there is a delay before any
operation is authorized (fan, cooling or heating). This can be used
to sequence start up multiple units/thermostat in one location.
10 to 120 seconds
Off: no room frost protection
On: room frost protection enabled in all system mode at: 42 F
(5.6 C)
Frost protection is enabled even in system Off mode
Off or On
Maximum occupied and unoccupied heating setpoint adjustment.
Heating setpoint range is: 40 F to 90 F (4.5 to 32.0 C)
Minimum occupied and unoccupied cooling setpoint adjustment.
Cooling setpoint range is: 54 F to 100 F (12.0 to 37.5 C)
Adjust the proportional band used by the thermostat PI control loop.
CAUTION
Note that the default value of 2.0 F (1.1 C) gives
satisfactory operation in most normal installation cases. The
use of a superior proportional band different than the factory
one is normally warranted in applications where the
thermostat location is problematic and leads to unwanted
cycling of the unit. A typical example is a wall mounted unit
where the thermostat is installed between the return and
supply air feeds and is directly influenced by the supply air
stream of the unit.
Value
F scale Pband
2
2 F
3
3 F
4
4 F
5
5 F
6
6 F
7
7 F
8
8 F
17
Adjustments
Schedules
Clock
setting
setting
Schedule
Clock
set Y/N
set Y/N
C scale Pband
1.1 C
1.7 C
2.2 C
2.8 C
3.3 C
3.9 C
4.4 C
Permanent
hold
Schedule
hold Y/N
62-2016—05