TEMPERATURE SETPOINTS
Permanent setpoint changes
This menu permits the adjustment of all permanent temperature setpoints (occupied and
unoccupied) as well as the desired temperature units (°F or °C) as shown in Table 7. Permanent
setpoints are written to RAM and EEPROM.
M16939
Temporary setpoint changes
Temporary setpoints can be modified through the Up arrow key ( ) and the Down arrow keys ( ).
User will be prompted with the present mode (Heating or Cooling) of the thermostat and its setpoint.
The Up ( ) arrow key will increment the setpoint by 0.5 degree (F or C). The Down ( ) arrow key will decrement the
setpoint by 0.5 degree (F or C). Press the Yes key to accept the new setpoint.
Local changes to the heating or cooling setpoints made by the user directly using the up or down arrow are temporary.
They will remain effective for the duration specified by ToccTime parameter.
Setpoints will revert back to their default value after internal timer ToccTime expires. If a permanent change to the
setpoints is required, use the Temperat set ? menu as described above in the Permanent Setpoint Changes section.
Table 7. Permanent Temperature Setpoint Changes User Menu Sequence
Cooling setpoint
Occupied mode
Cooling
No next
set?Y/N
Yes down
to set value, Yes key to confirm
Use
Cooling
Use
70.0°F
To set value
SYSTEM MODE SETTING
This menu is accessed to set system mode operation. Use
M16940
• Sys mode auto: Automatic changeover mode between heating and cooling operation
• Sys mode cooling: Cooling operation mode only
• Sys mode heating: Heating operation mode only
• Sys mode emergency: (Heat pump models only) Forced auxiliary heat operation mode only
• Sys mode off: Normal cooling or heating operation disabled. If enabled in installer parameters, only the automatic
heating frost protection at 50 F (10 C) is enabled
FAN MODE SETTING
This section of the menu is permits the setting of the fan mode operation. Use
Yes key to confirm
M16941
• Fan mode On: Fan is on continuously, even when system mode is OFF.
• Fan mode Auto: Fan cycles on a call for heating or cooling for both occupied and unoccupied periods.
• Fan mode Smart: During occupied periods, fan is on continuously. In unoccupied mode, fan cycles on a call for
heating or cooling. This selection is available on all models.
SCHEDULE SET (2 OR 4 EVENTS)
The scheduling option at the thermostat can only be used if the thermostat is not connected to
the WEBs-AX building control network. Once the thermostat is connected to the network, all
scheduling should be done through the WEBs-AX Workbench/Supervisor. Schedules set
through the network cannot be viewed on the thermostat. Thermostats with local scheduling can
have 2 or 4 events per day. Whether 2 or 4 events per day are allowed is set in the configuration
M16942
parameter 2/4 event.
If set for 2 events, the user can set two events per day, establishing occupied and unoccupied times. If set for 4 events,
the user can set four events per day, establishing occupied and unoccupied times. Each day can be tailored to specific
schedules if needed.
NOTE: 12:00 PM = Noon
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS
Heating setpoint
Occupied mode
Heating
No next
set?Y/N
Yes down
Heating
Use
68.00°F
To set value
Cooling setpoint
Unoccupied mode
Unocc CL
No next
set? Y/N
Yes down
Unocc CL
Use
80.0°F
To set value
11
Heating setpoint
Unoccupied mode
Unocc HT
No next
set? Y/N
Yes down
Unocc HT
Use
60.0°F
To set value
to set value, Yes key to confirm.
°F or °C
display setting
F or C
No next
set?Y/N
Yes down
Units
Use
°F
To set value
to set value,