Natural Gas BTU/h; for altitudes above from 0' to 4,500' above sea level, reduce input rating 4% for each 1,000' above 4,500' altitude. Low-fire rate is
1
75% of high-fire rate.
2
DOE AFUE based upon Isolated Combustion System (ICS)
3
Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in accordance with National Electrical
Codes. Extensive wire runs will require larger wire sizes.
4
Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size. May use fuses or HACR-type circuit breakers of
the same size as noted.
Notes
• All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
• Gas Service Connection ½" FPT
• Important: Size fuses and wires properly and make electrical connections in accordance with the National Electrical Code and/or all