FURNACE SPECIFICATIONS

MODEL
Btuh
Input (US)
Output (US)
Input (CAN)
Output (CAN)
A.F.U.E.
Rated External Static (" w.c.)
Tem perature Ris e (°F)
ID Blower Pres s ure Switch Trip Point (" w.c.)
Front Cover Pres s ure Switch Trip Point (" w.c.)
Blower Wheel (D" x W")
Blower Hors epower
Blower Speeds
Max CFM @ 0.5 E.S.P.
Power Supply
Minim um Circuit Am pacity (MCA)
Maxim um Overcurrent Device
Trans form er (VA)
Heat Anticipator (Am ps )
Prim ary Lim it Setting (°F)
Auxiliary Lim it Setting (°F)
Rollout Lim it Setting (°F)
Fan Delay On Heating
(1)
Off Heating
Fan Delay On Cooling
Off Cooling
Gas Supply Pres s ure (Natural/Propane) ("w.c.)
Manifold Pres s ure (Natural/Propane) ("w.c.)
Orifice Size (Natural/Propane)
Num ber of Burners
Vent Connector Diam eter (inches )
Com bus tion Air Connector Diam eter (inches )
Shipping Weight (lbs .)
(1)
Off Heating - This fan delay timing is adjustable (90, 120, 150 or 180 seconds), 150 seconds as shipped.
(2)
See Installation Instructions for approporiate vent pipe diameter, length and number of elbows.
(3)
See Installation Instructions for approporiate combustion pipe diameter, length and number of elbows.
1. These furnaces are manufactured for natural gas operation. Optional kits are available for conversion to propane operation.
2. For elevations above 2000 feet the rating should be reduced by 4% for each 1000 feet above sea level. The furnace must not
be derated, orifice changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufacturers method or in
accordance with the "A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING
CONTRACTORS OF AMERICA. The total heat loss calculated should be equal to or less than the heating capacity. Output
based on D.O.E. test procedures, steady state efficiency times output.
4. Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.
GMS95
0453BXA
46,000
44,400
46,000
44,400
95.0%
.20 - .50
35 - 65
-1.10
-0.37
10 x 8
1/3
4
1200
115-60-1
9.4
15.0
40
0.7
150
150
200
30 s ecs .
150 s ecs .
5 s ec.
45 s ecs .
7 / 11
3.5 / 10
43 / 55
2
(2)
2
(3)
2
132
GMS95
GMS95
GMS95
0703BXA
0704CXA
0904CXA
69,000
69,000
92,000
66,400
66,900
89,000
69,000
69,000
92,000
66,400
66,900
89,000
95.0%
95.0%
95.0%
.20 - .50
.20 - .50
.20 - .50
30 - 60
35 - 65
30 - 60
-0.95
-1.10
-1.20
-0.37
-0.37
-0.60
10 x 8
10 x 10
10 x 10
1/3
1/2
4
4
1200
1600
1600
115-60-1
115-60-1
115-60-1
9.4
13.8
13.8
15.0
15.0
15.0
40
40
0.7
0.7
0.7
160
160
150
150
150
150
200
200
200
30 s ecs .
30 s ecs .
30 s ecs .
150 s ecs .
150 s ecs .
150 s ecs .
5 s ec.
5 s ec.
5 s ec.
45 s ecs .
45 s ecs .
45 s ecs .
7 / 11
7 / 11
7 / 11
3.5 / 10
3.5 / 10
3.5 / 10
43 / 55
43 / 55
43 / 55
3
3
2
2
2
2
135
136
158
GMS95
GMS95
0905DXA
1155DXA
92,000
115,000
88,400
110,500
92,000
115,000
88,400
110,500
95.0%
95.0%
.20 - .50
.20 - .50
35 - 65
35 - 65
-1.10
-1.10
-0.37
-0.60
11 x 10
11 x 10
1/2
3/4
3/4
4
4
4
2000
2000
115-60-1
115-60-1
13.2
13.2
15.0
15.0
40
40
40
0.7
0.7
160
170
150
160
200
200
30 s ecs .
30 s ecs .
150 s ecs .
150 s ecs .
5 s ec.
5 s ec.
45 s ecs .
45 s ecs .
7 / 11
7 / 11
3.5 / 10
3.5 / 10
43 / 55
43 / 55
4
4
5
2
2
2
2
2
2
172
175
11