9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA

Phenomena
(1)LED2 on indoor controller board
is off.
Cause
• When LED1 on indoor controller board is also off.
Power supply of rated voltage is not supplied to out-
door unit.
Defective outdoor controller circuit board
Power supply of 208/230V is not supplied to indoor
unit.
Defective indoor controller board
(For the separate indoor/outdoor unit power sup-
ply system)
Power supply of 208/230V AC is not supplied to
indoor unit.
The connectors of the optional replacement kit are
not used.
Defective indoor controller board
• When LED1 on indoor controller board is lit.
Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address "0".)
20
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Check the voltage of outdoor power
supply terminal block (L1, L2).
• When AC 208/230V is not detected,
check the power wiring to outdoor unit
and the breaker.
• When AC 208/230V is detected, check
(below).
Check the voltage between outdoor
terminal block S1 and S2.
• When AC 208/230V is not detected,
—check the fuse on outdoor controller
circuit board.
—check the wiring connection.
• When AC 208/230V is detected, check
(below).
Check the voltage between indoor terminal
block S1 and S2.
• When AC 208/230V is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When AC 208/230V is detected, check
(below).
Check the fuse on indoor controller board.
Check the wiring connection.
If no problem are found, indoor controller
board is defective.
Check the voltage of indoor power supply
terminal block (L1,L2).
• When AC208/230V is not detected,
check the power supply wiring.
• When AC208/230V is detected, check
(below).
Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method
of connecting the connectors, connect
the connector correctly referring to
installation manual of an optional kit.
• When there is no problem in the meth-
od of connecting the connectors, check
(below).
Check the fuse on indoor controller board.
Check the wiring connection.
If no problem are found, indoor controller
board is defective.
Check again the setting of refrigerant
address for outdoor unit.
Set the refrigerant address to "0".
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to "0".)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
Countermeasure