Configuring Automatic on Battery Shutdown

If set to Off (default), the load segment turns off only when commanded manually by the
an external command, or through the display (Control > Load Segments).
If set to zero seconds (0s), the load segment turns off automatically when the UPS on Battery state
activates.
If you select a value, the load segment turns off automatically after the selected delay while the UPS
operates on battery, but the shutdown is cancelled if the utility returns before the delay has expired.
To set the shutdown times for each load segment:
1
Press the
button for longer than one second to go to the main menu selection and scroll down to
the Settings menu using the
2
Press the
button to enter the Settings menu.
3
Use the
button to scroll to the Automatic on Battery Shutdown option and press the
The options display and the current settings flash when selected.
4
Set the shutdown delay for one load segment using the
5
Press the
button to confirm.
6
Set the shutdown delay for the other load segment if applicable.
7
Press the
button to confirm.
button.
and
buttons.
Operation
button,
button.
|
51